D-EIMWC01405-18EN- 9/32
2
INSTALLATION
2.1
Storage
Should it be necessary to store the unit prior to installation, it is necessary to observe some precautions.
Do not remove the protective plastic
Do not leave the unit exposed to the elements
Do not expose the unit to direct sunlight
Do not use the machine near a heat source and/or open flame
Keep in places where room temperature is b 5° C to 55° C (room temperature over the maximum limit
may trigger the safety valve resulting in loss of refrigerant.
2.2
Receiving and handling
Inspect the unit immediately after delivery. In particular, make sure the machine is intact in all its parts and that there are
no deformations due to collisions. Should damages be found upon receipt, immediately file a written complaint with the
carrier.
Machine returns are Ex factory Daikin Applied Europe S.p.A.
Daikin Applied Europe S.p.A. cannot be held liable for any equipment damages incurred during transportation to the place
of destination.
The isolation of the evaporator corners, where the lifting holes are located, are shipped separately and must be assembled
on site after the unit has been permanently installed. Even the anti-vibration supports (optional) are shipped separately.
Make sure these items, if required, are delivered with the unit.
Use extreme caution when handling the unit to prevent damage to the control panel and the refrigerant pipes.
The unit must be lifted by inserting a hook in each of the four corners, where the lifting holes are located (see lifting
instructions). Distancer bars must be used along the line connecting the lifting holes to prevent damages to the electrical
panel and the compressor terminal box (see figure). Do not use any other point to lift the machine.
During the lifting phase, check that the lifting cords and/or chains do not touch the electrical panel and/or piping.
If, to move the machine, slides or moving skates are used, just push the base of the machine without touching the pipes,
compressors and/or electric panel.
Be careful not to hit, during handling, pipes, cables and installed accessories.
All the necessary devices guaranteeing personal safety must be provided during machine handling.
Refer to the dimensional drawing for hydraulic and electrical unit connections.
The overall machine dimensions, as well as the weights described in this manual, are purely
indicative.
The contract dimensional drawing and relevant wiring diagram are provided to the customer when
ordering.