Tasks carried out using user parameters

Defining the measurement unit

Depending on the setting of user parameter 

/23

 (measurement

unit), all temperature values are displayed in °C (=

0

) or in °F (=

1

).

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

Defining the time delay between pump and compressor 
startup

User parameter 

c07

 allows you to define the time delay between the

pump startup and the compressor startup.

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

Defining the time delay between unit and pump shutdown

User parameter 

c08

 allows you to define the time delay between the

unit shutdown and the pump shutdown, more specifically the period
during which the pump will still be active after the unit has been shut
down.

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

Defining the timer threshold for maintenance warning

User parameter 

c14

 allows you to define a timer threshold (running

hours of the compressor) after which the controller will generate a
maintenance warning or request.

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

Selecting local or remote cool/heat control

User parameter 

h06

 in combination with the remote cool/heat

selection switch (installed by the customer) allows the user to select
cooling or heating mode without using the 

D

 or 

C

 key on the

controller.

When user parameter 

h06

 is set to 

0

 (=not active), cooling or

heating mode is determined by means of the controller.

When user parameter 

h06

 is set to 

1

 (=active), cooling or

heating mode is determined by means of the remote switch.

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

Selecting local or remote on/off control

User parameter 

h07

 in combination with the remote on/off switch

(installed by the customer) allows the user to switch the unit on
without using the 

D

 or 

C

 key on the controller.

When user parameter 

h07

 is set to 

0

 (=not active), the unit can

only be switched on by means of the 

D

 and 

C

 key on the

controller.

When user parameter 

h07

 is set to 

1

 (=active), the unit can be

switched on or off as follows:

When remote on/off switch is opened, then the unit is
switched off and it is not possible to switch the unit on/off
while pressing the 

D

 or 

C

 key on the controller (5 sec).

When remote on/off switch is closed, then the unit is switched
on and it is possible to switch the unit on/off while pressing
the 

D

 or 

C

 key on the controller (5 sec).

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

Selecting dual setpoint control

User parameters 

p09

 (changeable digital selection S7S) and 

p34

(changeable digital selection S9S) can be used to assign the dual
setpoint control to S7S or S9S.

There are 3 different controls available for 2 different change digital
inputs (S7S and S9S):

p09

: changeable digital input selection S7S

0=no function

9=remote cool/heat

13=remote dual setpoint

p34

: changeable digital input selection S9S

0=no function

13=remote dual setpoint

23=remote on/off

When dual setpoint switch is open, the first setpoint is activated (

r01

cooling setpoint or 

r03

 heating setpoint, depending on cooling or

heating operation).

When dual setpoint switch is closed, the second setpoint is activated
(

r21

 cooling setpoint 2 or 

r22

 heating setpoint 2, depending on

cooling or heating operation).

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

NOTE

This is only in case 

p09

 (changeable digital input

selection S7S) has value 9 (default value).

In case dual setpoint function is selected for this
function (

p09

=13) then the remote cool/heat

control is not activated. Meaning the 

D

 or 

C

keys on the controller are still active.

NOTE

This is only in case 

p34

 (changeable digital input

selection S9S) has value 23 (default value).

In case dual setpoint function is selected for this
function (

p34

=13) then the remote on/off control

is not activated.

Summary of Contents for EWWP014KBW1N

Page 1: ...OPERATION MANUAL EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N Packaged water cooled water chillers...

Page 2: ...1 EWWP014KBW1N EWWP045KBW1N EWWP022KBW1N EWWP055KBW1N EWWP028KBW1N EWWP065KBW1N EWWP035KBW1N Packaged water cooled water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE U...

Page 3: ...led Model EWWP 045 055 065 Power supply Phase 3N Frequency Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal runn...

Page 4: ...O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected o...

Page 5: ...t from the water to prevent damage to the unit or blockage of the evaporator or condenser The water lter should be cleaned on a regular base Air purge valve delivered with the unit installed in the el...

Page 6: ...your local dealer 9 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identi cation label of the unit Water supply Fill...

Page 7: ...n page 8 Resetting alarms on page 8 Resetting warnings on page 8 Keys digital controller Keys remote interface Main display Sensor readout menu Parameter selection menu Parameter setting menu A T Pres...

Page 8: ...the setting of the selected parameter Only valid for read write parameters 7 Press the B key to con rm the modi ed setting OR Press the A key to cancel the modi ed setting 8 Press the A key to return...

Page 9: ...ror communication failure between the digital controller of the unit and the remote user interface Con rm the correct selection of parameter code h23 This should be default setting 0 and con rm the co...

Page 10: ...hreshold for maintenance warning c10 and c11 0 0 100 x100 hours R W U 241 I c15 Total running hours of pump x100 hours R D 126 A d No user or direct parameters accessible f No user or direct parameter...

Page 11: ...ss the A key to cancel the modi ed setting 11 Press the A key to return to the parameter group 12 Press 2 times the A key to return to the main display If during the procedure no buttons are pressed f...

Page 12: ...te on off switch installed by the customer allows the user to switch the unit on without using the D or C key on the controller When user parameter h07 is set to 0 not active the unit can only be swit...

Page 13: ...able with read only status the command will not be executed at all Variables requested by the supervisory system that are not available in a chiller with an address card are sent from the address card...

Page 14: ...s a user parameter refer to How to consult and modify the user parameters on page 10 Variables database The BMS or supervisory system and the chiller unit communicate through a xed set of variables al...

Page 15: ...s activated Refer to the explanation of the digital controller in the chapter Resetting alarms on page 8 The remote ON OFF input is enabled and the remote switch is off Put the remote switch on or dis...

Page 16: ...e electrical components are not damaged or loose Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened Refrigerant circuit Check for l...

Page 17: ...ect parameter setting values s p or levels l p a a l p function is not used Select parameter group Select parameter Read and modify parameter D C 2 D C 2 2 C B A A C D B C D C D C D C D C D C D C D C...