background image

EWWP014~065KBW1N

Packaged water-cooled water chillers

4PW61660-1A – 04.2012

Operation manual

14

T

ROUBLESHOOTING

This section provides useful information for diagnosing and correcting
certain troubles which may occur in the unit.

Before starting the trouble shooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.

Before contacting your local dealer, read this chapter carefully, it will
save you time and money.

When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no circum-
stances safety devices may be bridged or changed to a value other
than the factory setting. If the cause of the problem cannot be found,
call your local dealer.

Symptom 1: The unit does not start, but the 

L

 LED lights up

Symptom 2: The unit does not start, but the 

L

 LED is flashing

Symptom 3: The unit does not start and the 

L

 LED does not light up

Symptom 4: One of the following safety devices is activated

Symptom 5: Unit stops soon after operation

When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The temperature setting is not correct.

Check the controller setpoint.

Power supply failure.

Check the voltage on the supply 
panel.

Blown fuse or interrupted protection 
device.

Inspect fuses and protection devices. 
Replace by fuses of the same size 
and type (refer to chapter 

"Electrical 

specifications" on page 2

).

Loose connections.

Inspect connections of the field 
wiring and the internal wiring of the 
unit. Tighten all loose connections.

Shorted or broken wires.

Test circuits using a tester and repair 
if necessary.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The flowstart timer is still running.

The unit will start after approx. 15 
seconds. Make sure that water is 
flowing through the evaporator.

The anti-recycling timer is still active.

The circuit can only start up after 
approximately 6 minutes.

The guard timer is still active.

The circuit can only start up after 
approximately 1 minute.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

One of the following safety devices is 
activated:

• Reverse phase protector 
• Overcurrent relay (K*S)
• Discharge thermal protector (Q*D)
• Evaporating temperature 

thermostat (S*T)

• Flow switch (S10L)
• High pressure switch (S*HP)

Check on the controller and refer to 
symptom "4. One of the following 
safety devices is activated". Refer to 
the explanation of the digital 
controller in the chapter 

"Resetting 

alarms" on page 8

.

The unit is in anti-freeze alarm.

Check on the controller and refer to 
symptom "4. One of the following 
safety devices is activated". Refer to 
the explanation of the digital 
controller in the chapter 

"Resetting 

alarms" on page 8

The remote ON/OFF input is 
enabled and the remote switch is off.

Put the remote switch on or disable 
the remote ON/OFF input.

The keyboard is locked. The user 
parameter  

h09

 is set to 

0

.

Unlock the controller keyboard.

Symptom 4.1:  Overcurrent relay of compressor

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Failure of one of the phases.

Check fuses on the supply panel or 
measure the supply voltage.

Voltage too low.

Measure the supply voltage.

Overload of motor.

Reset. If the failure persists, call your 
local dealer.

RESET

Push the red button on the over-
current relay inside the switch box. 
The controller still needs to be reset.

Symptom 4.2:  Low pressure switch or anti-freeze alarm 

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow to water heat exchanger 
too low.

Increase the water flow.

Shortage of refrigerant.

Check for leaks and refill refrigerant, 
if necessary.

Unit is working out of its operation 
range.

Check the operation conditions of 
the unit.

Inlet temperature to the water heat 
exchanger is too low.

Increase the inlet water temperature.

Flow switch is not working or no 
water flow.

Check the flow switch and the water 
pump.

RESET

After pressure rise, the low pressure 
switch resets automatically, but the 
controller still needs to be reset.

Symptom 4.3:  High-pressure switch

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow through the condenser is 
too low.

Increase the water flow and/or check 
the strainer for clogging.

RESET

After pressure decrease, the high 
pressure switch resets automatically, 
but the controller still needs to be 
reset.

Symptom 4.4:  Reverse phase protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Two phases of the power supply are 
connected in the wrong phase 
position.

Invert two phases of the power 
supply (by licensed electrician).

One phase is not connected 
properly.

Check the connection of all phases.

RESET

After inverting two phases or fixing 
the power supply cables properly, 
the protector is reset automatically, 
but the unit still needs to be reset.

Symptom 4.5:  Discharge thermal protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Unit is working outside the operation 
range.

Check the operation condition of the 
unit.

RESET

After temperature decrease, the 
thermal protector resets 
automatically but the controller still 
needs to be reset.

Symptom 4.6:  Flow switch is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

No water flow.

Check the water pump.

RESET

After finding the cause, the flow 
switch is reset automatically, but the 
controller still needs to be reset.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

One of the safety devices is 
activated. 

Check safety devices (refer to 
symptom "4. One of the following 
safety devices is activated").

Voltage is too low.

Test the voltage in the supply panel 
and, if necessary, in the electrical 
compartment of the unit (voltage 
drop due to supply cables is too 
high).

Summary of Contents for EWWP014KBW1N

Page 1: ...OPERATION MANUAL EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N Packaged water cooled water chillers...

Page 2: ...1 EWWP014KBW1N EWWP045KBW1N EWWP022KBW1N EWWP055KBW1N EWWP028KBW1N EWWP065KBW1N EWWP035KBW1N Packaged water cooled water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE U...

Page 3: ...led Model EWWP 045 055 065 Power supply Phase 3N Frequency Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal runn...

Page 4: ...O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected o...

Page 5: ...t from the water to prevent damage to the unit or blockage of the evaporator or condenser The water lter should be cleaned on a regular base Air purge valve delivered with the unit installed in the el...

Page 6: ...your local dealer 9 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identi cation label of the unit Water supply Fill...

Page 7: ...n page 8 Resetting alarms on page 8 Resetting warnings on page 8 Keys digital controller Keys remote interface Main display Sensor readout menu Parameter selection menu Parameter setting menu A T Pres...

Page 8: ...the setting of the selected parameter Only valid for read write parameters 7 Press the B key to con rm the modi ed setting OR Press the A key to cancel the modi ed setting 8 Press the A key to return...

Page 9: ...ror communication failure between the digital controller of the unit and the remote user interface Con rm the correct selection of parameter code h23 This should be default setting 0 and con rm the co...

Page 10: ...hreshold for maintenance warning c10 and c11 0 0 100 x100 hours R W U 241 I c15 Total running hours of pump x100 hours R D 126 A d No user or direct parameters accessible f No user or direct parameter...

Page 11: ...ss the A key to cancel the modi ed setting 11 Press the A key to return to the parameter group 12 Press 2 times the A key to return to the main display If during the procedure no buttons are pressed f...

Page 12: ...te on off switch installed by the customer allows the user to switch the unit on without using the D or C key on the controller When user parameter h07 is set to 0 not active the unit can only be swit...

Page 13: ...able with read only status the command will not be executed at all Variables requested by the supervisory system that are not available in a chiller with an address card are sent from the address card...

Page 14: ...s a user parameter refer to How to consult and modify the user parameters on page 10 Variables database The BMS or supervisory system and the chiller unit communicate through a xed set of variables al...

Page 15: ...s activated Refer to the explanation of the digital controller in the chapter Resetting alarms on page 8 The remote ON OFF input is enabled and the remote switch is off Put the remote switch on or dis...

Page 16: ...e electrical components are not damaged or loose Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened Refrigerant circuit Check for l...

Page 17: ...ect parameter setting values s p or levels l p a a l p function is not used Select parameter group Select parameter Read and modify parameter D C 2 D C 2 2 C B A A C D B C D C D C D C D C D C D C D C...

Page 18: ......

Page 19: ......

Page 20: ...4PW61660 1A 2012 04 Copyright 2010 Daikin...

Reviews: