EWWP014~065KBW1N

Packaged water-cooled water chillers

4PW61660-1A – 04.2012

Operation manual

8

Consulting actual operational information

The actual operational information that can be consulted in the list of
direct parameters consists of:

b01

: Evaporator inlet water temperature,

b02

: Evaporator outlet water temperature,

b03

: When cooling mode is active: inlet water temperature of

the condenser. When heating mode is active: inlet water
temperature of the evaporator.

c10

: Total running hours of the compressor 1,

c11

: Total running hours of the compressor 2,

c15

: Total running hours of the pump.

These are direct parameters, refer to 

"How to consult and modify the

direct parameters" on page 7

.

Resetting alarms

When an alarm is detected, the following happens:

the alarm relay is energized,

the 

H

 LED is displayed

the display starts flashing, alternately showing the alarm code
and the inlet water temperature.

The following alarm codes may appear on the screen:

a1

: indicates an anti-freeze alarm.

e1

: indicates that the NTC probe used to measure the

evaporator inlet water temperature is defective.

e2

: indicates that the NTC probe used to measure the

evaporator outlet water temperature is defective.

e3

: indicates that the fuse for the evaporator heatertape (F4)

is blown or that there is a reverse phase error or that there
is a problem with the I/O PCB (A2P).

ehs

: indicates that the supply voltage is exceedingly high. In

this case contact a licensed electrician.

el1

: indicates that there is a power supply error (example:

noise). In this case contact a licensed electrician.

el2

: indicates that there is a power supply error (example:

noise). In this case contact a licensed electrician.

els

: indicates that the supply voltage is exceedingly low. In this

case contact a licensed electrician.

epb

: indicates that the EEPROM on the controller PCB inside

the unit is defective.

epr

: indicates that the EEPROM on the controller PCB inside

the unit is defective.

fl

: indicates that there was no sufficient water flow either

during the period of 15 seconds after the pump was
started or for 5 seconds while the compressor is active or
that the overcurrent protection of the pump is activated.

hp1

: indicates that a high pressure switch, the discharge

thermal protection or the overcurrent protection of the
compressor motor is activated or that the NTC probe used
to measure the ambient temperature is defective.

fl 

+

 hp1

: indicates that there is most likely an RPP error or that the

F4 fuse is blown.

lp1

: indicates that the low pressure switch is activated.

ter

: indicates that there is a remote user interface

communication error.

:

communication failure between the digital controller of the
unit and the remote user interface. Confirm the correct
selection of parameter code 

h23

. This should be default

setting 0 and confirm the correction installation according
to the installation manual of the remote user interface
EKRUMCA.

To reset an alarm, proceed as follows:

1

Find the cause of shutdown and correct.

Refer to the chapter 

"Troubleshooting" on page 14

.

2

If the alarm codes 

a1

fl

hp1

 or 

lp1

 appear on the display,

reset the alarm manually by pressing the 

E

 combination keys

C

 and 

D

 simultaneously for approximately 5 seconds.

In all other cases the alarm is reset automatically.

Once the alarm is reset, the error code and the 

H

 LED no longer

appears on the display. The controller continues its normal
operation, displaying the inlet water temperature.

Resetting warnings

During normal operation, the display of the controller may start
flashing, alternately showing the inlet water temperature and the
following warning code:

hc1

: indicates that the compressor 1 requires maintenance:

the total running hours of the compressor 

1 (direct

parameter 

c10

) has exceeded the setting of the timer

threshold for maintenance warning (user parameter

c14

).

hc2

: indicates that the compressor 2 requires maintenance:

the total running hours of the compressor 

2 (direct

parameter 

c11

) has exceeded the setting of the timer

threshold for maintenance warning (user parameter

c14

).

To reset the maintenance warning 

hc1

 or 

hc2

, proceed as follows:

1

Consult 

c10

 running hours of compressor 1 or 

c11

 running

hours of compressor 2.
These are direct parameters, refer to 

"How to consult and modify

the direct parameters" on page 7

.

2

When 

c10

 or 

c11

 parameter value is displayed, press the

C

 and 

D

 key simultaneously for 5 seconds. The value of

the timer becomes 

0

 and the warning is reset.

NOTE

The parameters 

b01

b02

 and 

b03

 can also be

consulted by the "sensor readout menu". Refer to

"How to consult the "sensor readout menu"
parameters" on page 7

.

To reset the timers of parameters 

c10

c11

 and

c15

 refer to 

"Resetting warnings" on page 8

.

In case the unit is equipped with freeze protection, it is
highly recommended to install the remote indicator
lamp alarm (H3P) (see wiring diagram supplied with
the unit). By doing so, breakdown of the fuse for the
evaporator heatertape (F4) will be detected sooner
and freezing of the circuit will be avoided during cold
weather.

NOTE

If the alarm codes 

fl

 and 

h1

 are flashing alternately,

the alarm is most probably caused by the reverse
phase protector or by the fuse for evaporator heater-
tape (F4) that was blown.

NOTE

Do not forget to carry out the required maintenance
activities after resetting the timers.

Besides resetting timer 

c10

 and 

c11

, it is also

possible to reset timer 

c15 

(running hours of pump) in

the same way.

Summary of Contents for EWWP014KBW1N

Page 1: ...OPERATION MANUAL EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N Packaged water cooled water chillers...

Page 2: ...1 EWWP014KBW1N EWWP045KBW1N EWWP022KBW1N EWWP055KBW1N EWWP028KBW1N EWWP065KBW1N EWWP035KBW1N Packaged water cooled water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE U...

Page 3: ...led Model EWWP 045 055 065 Power supply Phase 3N Frequency Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal runn...

Page 4: ...O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected o...

Page 5: ...t from the water to prevent damage to the unit or blockage of the evaporator or condenser The water lter should be cleaned on a regular base Air purge valve delivered with the unit installed in the el...

Page 6: ...your local dealer 9 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identi cation label of the unit Water supply Fill...

Page 7: ...n page 8 Resetting alarms on page 8 Resetting warnings on page 8 Keys digital controller Keys remote interface Main display Sensor readout menu Parameter selection menu Parameter setting menu A T Pres...

Page 8: ...the setting of the selected parameter Only valid for read write parameters 7 Press the B key to con rm the modi ed setting OR Press the A key to cancel the modi ed setting 8 Press the A key to return...

Page 9: ...ror communication failure between the digital controller of the unit and the remote user interface Con rm the correct selection of parameter code h23 This should be default setting 0 and con rm the co...

Page 10: ...hreshold for maintenance warning c10 and c11 0 0 100 x100 hours R W U 241 I c15 Total running hours of pump x100 hours R D 126 A d No user or direct parameters accessible f No user or direct parameter...

Page 11: ...ss the A key to cancel the modi ed setting 11 Press the A key to return to the parameter group 12 Press 2 times the A key to return to the main display If during the procedure no buttons are pressed f...

Page 12: ...te on off switch installed by the customer allows the user to switch the unit on without using the D or C key on the controller When user parameter h07 is set to 0 not active the unit can only be swit...

Page 13: ...able with read only status the command will not be executed at all Variables requested by the supervisory system that are not available in a chiller with an address card are sent from the address card...

Page 14: ...s a user parameter refer to How to consult and modify the user parameters on page 10 Variables database The BMS or supervisory system and the chiller unit communicate through a xed set of variables al...

Page 15: ...s activated Refer to the explanation of the digital controller in the chapter Resetting alarms on page 8 The remote ON OFF input is enabled and the remote switch is off Put the remote switch on or dis...

Page 16: ...e electrical components are not damaged or loose Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened Refrigerant circuit Check for l...

Page 17: ...ect parameter setting values s p or levels l p a a l p function is not used Select parameter group Select parameter Read and modify parameter D C 2 D C 2 2 C B A A C D B C D C D C D C D C D C D C D C...

Page 18: ......

Page 19: ......

Page 20: ...4PW61660 1A 2012 04 Copyright 2010 Daikin...

Reviews: