background image

EWWP045~06 ECB2+3MUAW

Packaged water-cooled water chillers

4PW61663-1A - 2012.04

Installation manual

3

W

ATER

 

QUALITY

 

SPECIFICATIONS

 

A = corrosion 

B = scale

C

ONNECTING

 

THE

 

WATER

 

CIRCUIT

The evaporator and condenser are foreseen of GAS male pipe thread
for the water inlet and outlet (refer to the outlook diagram).
Evaporator and condenser water connections are to be made in
accordance with the outlook diagram, respecting the water in- and
outlet.

If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
the water circuit:

1.

Use clean pipes only.

2.

Hold the pipe end downwards when removing burrs.

3.

Cover the pipe end when inserting it through a wall so that no dust
and dirt enter.

W

ATER

 

CHARGE

FLOW

 

AND

 

QUALITY

To assure proper operation of the unit a minimum water volume is
required in the system and the water flow through the evaporator
must be within the operation range as specified in the table below.

P

IPING

 

INSULATION

The complete water circuit, inclusive all piping, must be insulated to
prevent condensation and reduction of the cooling capacity.

Protect the water piping against water freezing during winter period
(e.g. by using a glycol solution or heatertape).

F

IELD

 

WIRING

 

Installing the control box (ECB*MUAW)

Follow instructions in "

Annex

" (32~72 Hp) at the very end of this 

manual

 

when installing the control box into the unit.

Parts table

F1,2,3U .................. Main fuses for the unit

H1P........................ Indication lamp alarm

H3P........................ Indication lamp operation compressor

PE .......................... Main earth terminal

S7S ........................ Remote cooling/heating change-over valve

S9S ........................ Remote start/stop switch

S10L ...................... Flowswitch

S11L ...................... Contact that closes if the pump is working

S12S ...................... Main isolator switch

- - - ......................... Field wiring

Power circuit and cable requirements

1

The electrical power supply to the unit should be arranged so
that it can be switched on or off independently of the electrical
supply to other items of the plant and equipment in general.

2

A power circuit must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a
circuit breaker, a slow blow fuse on each phase and an earth
leak detector. Recommended fuses are mentioned on the wiring
diagram supplied with the unit. 

evaporator water

condenser water

circulating 

water

[<20°C]

supply 

water

circulating 

water

[20°C~60°C]

supply 

water

tendency 

if out of 

criteria

Items to be controlled

pH

at 25°C

6.8~8.0

6.8~8.0

7.0~8.0

7.0~8.0

A + B

Electrical 
conductivity

[mS/m]

at 25°C

<40

<30

<30

<30

A + B

Chloride ion

[mg Cl

/l]

<50

<50

<50

<50

A

Sulfate ion

[mg SO

4

2–

/l]

<50

<50

<50

<50

A

M-alkalinity 
(pH 4.8)

[mg CaCO

3

/l]

<50

<50

<50

<50

B

Total hardness

[mg CaCO

3

/l]

<70

<70

<70

<70

B

Calcium 
hardness

[mg CaCO

3

/l]

<50

<50

<50

<50

B

Silica ion

[mg SiO

2

/l]

<30

<30

<30

<30

B

Items to be referred to

Iron

[mg Fe/l]

<1.0

<0.3

<1.0

<0.3

A + B

Copper

[mg Cu/l]

<1.0

<0.1

<1.0

<0.1

A

Sulfide ion

[mg S

2–

/l]

not detectable

A

Ammonium ion

[mg NH

4

+

/l]

<1.0

<0.1

<0.3

<0.1

A

Remaining 
chloride

[mg Cl/l]

<0.3

<0.3

<0.25

<0.3

A

Free carbide

[mg CO

2

/l]

<4.0

<4.0

<0.4

<4.0

A

Stability index

A  +  B

Minimum 

water volume (l)

Minimum 

water flow

Maximum 

water flow

32 Hp

205

202 l/min

493 l/min

36 Hp

268

232 l/min

568 l/min

40 Hp

268

262 l/min

642l/min

44 Hp

311

283 l/min

694 l/min

48 Hp

311

304 l/min

745 l/min

52 Hp

205

333 l/min

814 l/min

56 Hp

205

363 l/min

889 l/min

60 Hp

268

393 l/min

963 l/min

64 Hp

268

414 l/min

1015 l/min

68 Hp

268

435 l/min

1066 l/min

72 Hp

311

456 l/min

1118 l/min

The water pressure should not exceed the maximum
working pressure of 10 bar.

NOTE

Provide adequate safeguards in the water circuit to
make sure that the water pressure will never exceed
the maximum allowable working pressure.

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.

The field wiring must be carried out in accordance with the
wiring diagram supplied with the unit and the instructions
given below.

Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.

Switch off the main isolator switch before making any
connections (switch off the circuit breaker, remove or
switch off the fuses).

Summary of Contents for EWWP045KAW1M

Page 1: ...INSTALLATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB2MUAW ECB3MUAW Packaged water cooled water chillers...

Page 2: ...B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Informatio...

Page 3: ...d features 1 Options Glycol application for leaving evaporator water down to 10 C or 5 C Low noise operation kit field installation Features Voltage free contacts general operation pumpcontact alarm R...

Page 4: ...ated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R407C GWP 1 value 1652 5 1 GWP global warming potential The refrigerant quantity is indicated...

Page 5: ...circuit must be provided for connection of the unit This circuit must be protected with the required safety devices i e a circuit breaker a slow blow fuse on each phase and an earth leak detector Rec...

Page 6: ...g site of the refrigeration system 1 European International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipmen...

Page 7: ...ircuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergency...

Page 8: ......

Page 9: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 ANNEX Installing the control box 1 2 3...

Page 10: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 2 3 4 1...

Page 11: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 2 2 1 1 8 x 4 x 2 2 1 1 3 3 4 4 5 5...

Page 12: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 2 2 1 1 3 3 8 x 8 x 2 2 1 1 3 3 4 4 6 6 5 5...

Page 13: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4...

Page 14: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 3 3 2 2 1 1...

Page 15: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 3 3 4 4 2 2 1 1...

Page 16: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 1 1 2 2 1 1 1 1 2 2 2 2...

Page 17: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 1 1 2 2 3 3 1 1 1 1 2 2 2 2 3 3 3 3...

Page 18: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 1 1 5 5 4 4 3 3 2 2 50 Hz 3 x 400 V...

Page 19: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 4 x 6 x...

Page 20: ...4PW61663 1A 2012 04 Copyright 2010 Daikin...

Reviews: