ESIE07-05
The Digital Controller
Part 2 – Functional Description
2–23
3
2
4
5
1
1.5.1
Main Menu
Introduction
This menu shows only the output parameters throughout the screens listed below (the passage from
one to another is allowed by the arrow key).
Current date, time and weekday, setpoint origin and unit status in percent with the possibilities listed
below.
Setpoint source
■
Local
■
Double
■
Ret. Reset
Evaporator
outlet/inlet water
temperature
This screen shows the Evaporator outlet/inlet water temperature (or common temperature for two
evaporators units)
First and second evaporator outlet temperature (two evaporators units)
Possible status :
■
Off Alarm
: unit Off for alarm
■
Off Rem Comm
: unit Off by remote communication (supervisor or BMS)
■
Off Time Schedule
: unit Off by time schedule
■
Off Loc/Remote Sw
: unit Off through switch
■
Off Keypad
: unit Off through keypad (key on/off)
■
Off Amb. LockOut
: unit Off by low ambient temperature (or tower return temperature)
■
Waiting flow
: unit On waiting for evaporator water flow
■
Waiting load
: unit On without compressors in motion because not required by
load.
■
No comps available
: unit On with no compressors available for automatic management
(compressor switch OFF or alarm or in manual mode)
gg/mm/aa
Unit
Cooling
Stp Source:
Sat
status
staging
Local
hh:mm
xxx%
COMPRESSOR #1 STATUS
Compressor off
COMPRESSOR #2 STATUS
COMPRESSOR #3 STATUS
COMPRESSOR #4 STATUS
Unit Status
Setpoint Source
Compressor on
Compressor disabled or alarm
X
Water Temperatures
ENT Evap
=
xxx ˚C
LVG Evap
=
xxx ˚C