ESIE07-05
The Digital Controller
Part 2 – Functional Description
2–13
3
2
4
5
1
1.4.5
Addressing of pLAN
To get the correct functionality of the pLAN net system, it is necessary to address correctly all the
installed components. Each component has a series of microswitches that must be set as specified in
the table below.
pLAN component
Microswitches
1
2
3
4
5
6
Local DISPLAY
OFF
OFF
OFF
OFF
ON
OFF
Remote DISPLAY
(if available)
ON
OFF
OFF
OFF
ON
OFF
COMP. BOARD #1
ON
OFF
OFF
OFF
OFF
OFF
COMP. BOARD #2
OFF
ON
OFF
OFF
OFF
OFF
COMP. BOARD #3
ON
ON
OFF
OFF
OFF
OFF
COMP. BOARD #4
OFF
OFF
ON
OFF
OFF
OFF
DRIVER EXV #1
ON
OFF
ON
OFF
OFF
OFF
DRIVER EXV #2
ON
ON
ON
OFF
OFF
OFF
DRIVER EXV #3
ON
OFF
OFF
ON
OFF
OFF
DRIVER EXV #4
ON
ON
OFF
ON
OFF
OFF
ESIE07-05.book Page 13 Friday, December 21, 2007 3:21 PM