–EIMHP01201-18_04EN - 8/24
2.2
Operating limits Air to Water operation
Cooling Mode:
Heating Mode:
The following options must be included according to the specific operating area:
Ref. area 1: standard unit
(no options are required to operate in this area)
Ref. area 2: standard unit - opt. 08 (Brine) (unit may not unload to minimum load)
Ref. area 3: standard unit - opt. 142 (High Ambient kit)
Note:
•
The above graph refers to the unit operating at full load. Unit may be able to operate outside the above envelope
with compressors unloading. Please contact factory for further details.
•
For operation with temperature at the outlet of the cold heat exchanger below +4°C, the unit must operate with
glycol mixture (ethylene or propylene glycol). The glycol percentage must be provided according to the minimum
ELWT needed.
•
The above graphic represents a guideline about the operating limits of the range. Please refer to the latest Chiller
Selection Software (CSS) for real operating limits working conditions for each size.