15
|
About the units and options
Installer and user reference guide
47
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
15 About the units and options
In this chapter
15.1 Identification
15.1.1 Identification label: Indoor unit
Location
15.2 About the indoor unit
Use the system in the following temperature and humidity ranges for safe and
effective operation.
For combination with R410A outdoor unit, refer to the following table:
Outdoor units
Cooling
Heating
RZQ200
Outdoor
temperature
–5~46°C DB
–15~15°C WB
Indoor
temperature
14~28°C WB
10~27°C DB
RZQG71~140
Outdoor
temperature
–15~50°C DB
–20~15.5°C WB
Indoor
temperature
12~28°C WB
10~27°C DB
RZQSG71~140
Outdoor
temperature
–15~46°C DB
–15~15.5°C WB
Indoor
temperature
14~28°C WB
10~27°C DB
Indoor humidity
≤80%
(a)
—