CAUTION

When clamping wiring, use the included clamping material and clamp firmly to prevent outside pressure 
being exerted on the wiring connections.
When doing the wiring, make sure the wiring is neat and does not cause the control box lid to stick up, then 
close the cover firmly.
When attaching the control box lid, make sure you do not pinch any wires.
After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (pro-
cured locally) to prevent small animals and insects from entering the unit from outside.
(If any do get in, they can cause short circuits in the control box.)
Outside of the unit, separate low-voltage wires (remote controller cords) by a minimum of 50 mm from high-
voltage wires (inter-unit lines, ground lines, and other electrical lines) to avoid routing the two through the 
same locations. Proximity may cause electrical interference, malfunctions, and breakage.

[ Precautions for wiring ]

2 power wires of different diameters cannot be connected to the power terminal block. 
(Slack in the power wiring may cause abnormal heating.)
Use sleeve-insulated round pressure terminals for connections to the power terminal block.
If none are available, connect wires of the same diameter to both sides, as shown in the figure.

Follow the instructions are right if the wiring may get very hot due to slack in the power wiring.

For wiring, use the designated power wire and connect firmly, then secure using the included clamping 
material to prevent outside pressure being exerted on the terminal board.

Use the correct size of screwdriver when tightening the terminal screws. A screwdriver with a small head 
will strip the screw heads and make proper tightening impossible.

Over-tightening the terminal screws may break them.

For the tightening torque of the terminal screws, refer to the table below.

Tightening torque (N·m)

Remote controller wiring terminal block

0.79~0.97

Inter-unit wiring terminal block 

1.18~1.44

Ground terminal

1.44~1.94

Connect same-thickness
wiring to both sides.

GOOD

WRONG

WRONG

It is forbidden to 
connect the two 
wires to one side.

Fig. 19

It is forbidden to 
connect wiring of 
different thicknesses.

Power wire

Insulating sleeve

Round pressure 
terminal

01_EN_3P184443-2.fm  Page 12  Monday, July 3, 2006  3:14 PM

Summary of Contents for FAY71FJV1

Page 1: ...SAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO...

Page 2: ...reenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Page 3: ...guinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retningsgivende dokument er for...

Page 4: ...ry out installation work Do not try to install the machine your self Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this install...

Page 5: ...chen Plastic parts may deteriorate and fall off or result in water leakage b where corrosive gas such as sulfurous acid gas is produced Corroding copper pipes or soldered parts may result in refrigera...

Page 6: ...ote controller from Table 1 according to customer request and install in an appropriate place For installation follow the Installation manual included with the remote controllers Table 1 NOTE If the c...

Page 7: ...of the outdoor unit Items to be checked If not properly done what is likely to occur Check Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test finished It may...

Page 8: ...installation panel is attached to the rear of the unit To detach remove the screws from the bottom of the panel Refer to Fig 1 2 Attach the installation panel to the wall using the paper pattern for i...

Page 9: ...ok on the installation panel Refer to Fig 4 and 5 If running pipes from the left side or using embedded pipes remove the bottom panel to make work easier CAUTION Install the unit so that it is level o...

Page 10: ...wrong refrigerant will prevent the unit from functioning properly CAUTION Use a pipe cutter and flare suitable for the type of refrigerant Apply ester oil or ether oil around the flare section before...

Page 11: ...are leaking After checking for gas leaks in the pipe connections insulate them as shown in Fig 11 and 12 Install so that no pipes are exposed as this may cause leaking Pipe size Further tightening ang...

Page 12: ...igerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains fluorine it will damage the refrigerant oil Before brazing loc...

Page 13: ...it through the drain pipes and corrode the heat exchanger 7 ELECTRIC WIRING WORK All field supplied parts and materials and electric works must conform to local codes Use copper wire only For electric...

Page 14: ...nal board Remote controller cord connections not necessary for slave unit of simultaneous operation system Feed wires through the clamp and connect to the terminal board for transmission wiring no po...

Page 15: ...lack in the power wiring may cause abnormal heating Use sleeve insulated round pressure terminals for connections to the power terminal block If none are available connect wires of the same diameter t...

Page 16: ...he remote controller that suits the indoor unit which has the most functions as attached swing flap 4 For simultaneous operation system connect the remote controller cord to the master unit 1 2 3 P1 P...

Page 17: ...e installation manual attached to the wireless remote controller for setting instructions 3 Setting indoor unit number of simultaneous operation system When using in simultaneous operation system mode...

Page 18: ...ler from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the remote controller terminal board of the master unit 5 CONTROL BY 2 REMOTE CON...

Page 19: ...function diagnoses below 2 HOW TO DIAGNOSE FOR PROBLEMS With the power on Troubles can be monitored on the remote controller or the LED s on the PC board of the indoor unit Trouble shooting with the d...

Page 20: ...rmal mode 3 Depending on the model or the conditions it may carry out an emergency shut down 4 If the HBP H2P is off the branch wiring between each of the indoor and outdoor units may either be incorr...

Page 21: ...utdoor unit E1 Outdoor unit s PC board faulty outdoor unit E3 High pressure abnormal outdoor unit E4 Low pressure abnormal outdoor unit E5 Compressor motor lock malfunction outdoor unit E7 Outdoor fan...

Page 22: ...s shown the wiring between the indoor and outdoor units is not properly wired Therefore immediately disconnect the power supply and correct the wiring The com pressor and the fan mounted on the outdoo...

Page 23: ...OLLER KIT IS BEING USED 5 REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM CONFIRM ENGINEERING MATERIALS AND CATALOGS ETC BEFORE CONNECTING 6 SYMBOLS SHOW AS FOLLOWS RED RED BLK BLAC...

Page 24: ...YSTEM CONFIRM ENGINEERING MATERIALS AND CATALOGS ETC BEFORE CONNECTING 6 SYMBOLS SHOW AS FOLLOWS RED RED BLK BLACK WHT WHITE YLW YELLOW ORG ORANGE GRY GRAY PRP PURPLE BLU BLUE 7 CONFIRM THE METHOD OF...

Page 25: ...0608 HT 3P184443 2 EM00A030E 00_CV_3P184443 2 fm Page 2 Monday July 3 2006 2 21 PM...

Reviews: