9. FIELD SETTING
Field setting must be made from the remote controller in accordance with the installation condition.
•
Setting can be made by changing the “Mode No.”, “FIRST CODE NO.”, and “SECOND CODE NO.”.
•
For setting and operation, refer to the “FIELD SETTING” in the installation manual of the remote controller.
1. Setting air filter sign
•
Remote controllers are equipped with liquid crystal display air filer signs to display the time to clean
air filters.
•
Change the SECOND CODE NO. according to Table 5 depending on the amount of dirt or dust in the
room.
(SECOND CODE NO. is factory set to “01” for filter contamination-light)
Table 5
2. Setting air flow rate increase mode
•
It is possible to raise set air flow (HIGH and LOW) from the field. Change the SECOND CODE NO. as
shown in Table 6 to suit your needs.
(SECOND CODE NO. is factory set to “01” for standard.)
Table 6
〈
When using wireless remote controllers
〉
•
When using wireless remote controllers, wireless remote controller address setting is necessary.
Refer to the installation manual attached to the wireless remote controller for setting instructions.
3. Setting indoor unit number of simultaneous operation system
•
When using in simultaneous operation system mode, change the SECOND CODE NO. as shown in
Table 7.
(SECOND CODE NO. is factory set to “01” for pair system.)
Table 7
•
When using in simultaneous operation system mode, refer to
“Simultaneous Operation System
Individual Setting”
section to set master and slave units separately.
〈
When using wireless remote controllers
〉
•
When using wireless remote controllers, wireless remote controller address setting is necessary.
Refer to the installation manual attached to the wireless remote controller for setting instructions.
Setting
Spacing time of display air
filter sign
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Air filter
contamination-light
Approx. 200 hrs.
10 (20)
0
01
Air filter
contamination-heavy
Approx. 100 hrs.
02
Setting
Mode No.
FIRST CODE NO.
SECOND CODE NO.
Standard
13(23)
0
01
A little increase
02
Increase
03
Setting
Mode No.
FIRST CODE NO.
SECOND CODE NO.
Pair system (1 unit)
11 (21)
0
01
Simultaneous operation
system (2-unit)
02
Simultaneous operation
system (3-unit)
03