4P561448-1B – 2021.07
7 Configuration
7.1 Field setting
Make the following field settings so that they correspond with the actual
installation setup and with the needs of the user:
▪
Ceiling height
▪
Design decoration panel (if applicable)
▪
Air flow direction
▪
Air volume when thermostat control is OFF
▪
Time to clean air filter
Setting: Ceiling height
This setting must correspond with the actual distance to the floor, capacity class
and airflow directions.
▪
For 3-way and 4-way airflow (which require an optional blocking pad kit), see the
installation manual of the optional blocking pad kit.
▪
For all-round air flow, use the table below.
If the distance to the floor is (m)
Then
(1)
FCAG35~71
FCAG100~140
M
C1
C2
≤2.7
≤3.2
13 (23)
0
01
2.7<x≤3.0
3.2<x≤3.6
02
3.0<x≤3.5
3.6<x≤4.2
03
Setting: Decoration panel type
When installing or changing the decoration panel type, ALWAYS check if the
correct values are set.
If the … decoration panel is used
Then
(1)
M
C1
C2
Standard or self-cleaning
13 (23)
15
01
Design
02
Setting: Air flow direction
This setting must correspond with the actual used air flow directions. See the
installation manual of the optional blocking pad kit and the manual of the user
interface.
Default: 01 (= all-round air flow)
Example:
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
C1
: First code number
•
C2
: Second code number
•
: Default