background image

 

FCQ35~14 FCQH71~140C7VEB
Split System air conditioners
4PW31577-1B

Installation manual

4

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Execute heat insulation work completely on both sides of the gas
piping and liquid piping. Otherwise, this can sometimes result in
water leakage.

Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for R410A refrigerant.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

The outdoor unit is charged with refrigerant.

To  prevent water leakage, execute heat insulation work
completely on both sides of the gas and liquid piping. When
using a heat pump, the temperature of the gas piping can reach
up to approximately 120°C, use insulation which is sufficiently
heat resistant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc. inside the refrigerant circuit.

Refer to 

Table 1

 for the dimensions of flare nut spaces and the

appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

Table 1

When connecting the flare nut, coat the flare both inside and
outside with refrigerating ether or ester oil and initially tighten by
hand 3 or 4 turns before tightening firmly.
Coat here with ether oil or ester oil

If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a
fire.

Make sure there is no refrigerant gas leak. A toxic gas may be
released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.

Finally, insulate as shown in the figure below (use the supplied
accessory parts)

Piping insulation procedure

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

Pipe gauge

Tightening torque

Flare dimension 

A (mm)

Flare shape

Ø6.4

14.2~17.2 N•m

8.7~9.1

Ø9.5

32.7~39.9 N•m

12.8~13.2

Ø12.7

49.5~60.3 N•m

16.2~16.6

Ø15.9

61.8~75.4 N•m 

19.3~19.7

1

2

3

4

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

R0.4~0.8

45

° ±

2

90

°±

2

A

Gas piping

Liquid piping

1

Piping insulation material (field supply)

2

Flare nut connection

3

Insulation for fitting (delivered with the unit)

4

Piping insulation material (main unit)

5

Main unit

6

Clamp (field supply)

7

Medium 1 sealing pad for gas piping (delivered with the unit)
Medium 2 sealing pad for liquid piping (delivered with the unit)

A

Turn seams up

B

Attach to base

C

Tighten the part other than the piping insulation material

D

Wrap over from the base of the unit to the top of the flare nut 
connection

For local insulation, be sure to insulate local piping all
the way into the pipe connections inside the unit.

Exposed piping may cause condensation or may
cause burns when touched.

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1
2

5

3

4
5

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting for liquid 
pipe

4

Insulation for fitting for gas 
pipe

5

Clamps 
(use 2 clamps per insulation)

A

B

D

C

7

1

2

3

4

5

6

6

A

B

C

1

2

3

4

5

6

6

D

7

1

2

3

4

5

6

6

Downloaded from AC-Manual.com Manuals

Summary of Contents for FCQ35C7VEB x 3

Page 1: ...ION MANUAL FCQ35C7VEB FCQ50C7VEB FCQ60C7VEB FCQ71C7VEB FCQ100C7VEB FCQ125C7VEB FCQ140C7VEB FCQH71C7VEB FCQH100C7VEB FCQH125C7VEB FCQH140C7VEB Split System air conditioners Downloaded from AC Manual co...

Page 2: ...1500 3 2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 2 8 2 2 5 10 6 7 5 6 10 8 3 6 4 3 1 2 5 4 1 3 2 5 6 8 11 4 7 9 10 Downlo...

Page 3: ...instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te ga v i teiste normati...

Page 4: ...the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied pa...

Page 5: ...t at a height over 2 7 m for FCQH100 140 units 3 2 m To avoid accidental touching it is recommended to install the unit higher than 2 5 m Refer to Field setting on page 8 and to the decoration panel i...

Page 6: ...urements of the ceiling opening Consult the builder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit cas...

Page 7: ...shown in the figure below use the supplied accessory parts Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying out nitrogen rep...

Page 8: ...ed up 75 mm Testing of drain piping After the piping work is finished check if drainage flows smoothly Add approximately 1 l of water gradually through the air discharge outlet Method of adding water...

Page 9: ...nect to the remote controller wiring terminal block Securely fix the wiring using a clamp as indicated in the figure After connection Attach the small sealing supplied with the unit around the cables...

Page 10: ...anual attached to the outdoor units Confirm the system type Pair type or multi system 1 remote controller controls 1 indoor unit standard system Simultaneous operation system 1 remote controller contr...

Page 11: ...ing the master and slave unit separately Procedure See figure 17 1 Change the Second code No to 02 individual setting so that the slave unit can be individually set Second code No is factory set to 01...

Page 12: ...wired remote controller and start operation by pushing ON OFF button 5 Press Inspection Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation...

Page 13: ...lector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector adaptor for wiring X35A Connector group control ad...

Page 14: ...NOTES NOTES Downloaded from AC Manual com Manuals...

Page 15: ...2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 5 6 4 8 4...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW31577 1B Downloaded from AC Manual com Manuals...

Reviews: