Field Settings
SiUS071735EA
121
Trial Operation and Field Settings
4.2
Overview of the Field Settings
: Factory setting
Note:
The SECOND CODE NO. is factory set to "01".
Do not use any settings not listed in the table. For group control with a wireless remote controller,
initial settings for all the indoor units of the group are equal. (For group control, refer to the
installation manual attached to the indoor unit for group control.)
External Static Pressure Settings
09/12 class
: Factory setting
15/18/24 class
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01
02
03
04
05
06
10
(20)
0
Filter cleaning
sign interval
(used to change
filter cleaning
display interval
according to filter
contamination)
Longlife
filter
Li
ght
Approx.
2,500
hrs.
He
a
v
y
Approx.
1,250
hrs.
—
—
—
—
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
—
—
—
—
3
Filter cleaning sign (used to
set filter cleaning display ON/
OFF)
Display
No display
—
—
—
—
11
(21)
7
Air volume adjustment
OFF
Air volume
adjustment
completion
Air volume
adjustment
start
—
—
—
13
(23)
6
External static pressure
Refer to the table below.
Mode No.
First Code No.
Second Code No.
Contents
13(23)
6
03
30 Pa
04
40 Pa
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
10
100 Pa
11
110 Pa
12
120 Pa
13
130 Pa
14
140 Pa
15
150 Pa
Mode No.
First Code No.
Second Code No.
Contents
13(23)
6
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
10
100 Pa
11
110 Pa
12
120 Pa
13
130 Pa
14
140 Pa
15
150 Pa
Summary of Contents for FDMQ-R Series
Page 12: ...SiUS071735EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiUS071735EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 120: ...Check SiUS071735EA 109 Service Diagnosis 15 18 24 class R25105 1 2 3 4 Multimeter...
Page 122: ...Check SiUS071735EA 111 Service Diagnosis 15 18 24 class R20704 W V U DC_P1 DC_N1...
Page 140: ...Piping Diagrams SiUS071735EA 129 Appendix RX24RMVJU A 3D092249A...