Main Functions
SiUS071735EA
19
Functions and Control
1.4
Program Dry Operation
Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and
FAN
setting buttons are inoperable.
Details
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two zones.
Then, the unit operates in an appropriate capacity for each zone to maintain the temperature and
humidity at a comfortable level.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24.5°C or more
(76.1°F or more)
Room thermistor
temperature at start-up
X – 2.5°C
(X – 4.5°F)
X – 1.0°C
(X – 1.8°F)
16.5 ~ 24°C
(61.7 ~ 75.2°F)
X – 2.0°C
(X – 3.6°F)
X – 1.0°C
(X – 1.8°F)
16°C or less
(60.8°F or less)
16°C
(60.8°F)
X – 2.0°C
(X – 3.6°F)
X – 1.0°C = 15°C
(X – 1.8°F = 59°F)
Zone A = Thermostat OFF
Target temperature X
Zone B
Room temperature
Room temperature
Zone C = Thermostat ON
Y = X – 2.5
°
C (4.5
°
F)
or
Y = X – 2.0
°
C (3.6
°
F)
Z = X – 1.0
°
C (1.8
°
F)
X – 1.0
°
C (1.8
°
F)
(R24367)
Summary of Contents for FDMQ-R Series
Page 12: ...SiUS071735EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiUS071735EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 120: ...Check SiUS071735EA 109 Service Diagnosis 15 18 24 class R25105 1 2 3 4 Multimeter...
Page 122: ...Check SiUS071735EA 111 Service Diagnosis 15 18 24 class R20704 W V U DC_P1 DC_N1...
Page 140: ...Piping Diagrams SiUS071735EA 129 Appendix RX24RMVJU A 3D092249A...