SiUS071735EA
Control Specification
Functions and Control
42
2. When the operation mode is heating
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe tempe6°C (+10.8°F) < indoor heat exchanger temperature
When the thermistor is disconnected
When the disconnection is ascertained, the compressor continues operation for 9 minutes and then
stops.
If the compressor stops repeatedly, the system is shut down.
2.11.8 Target Discharge Pipe Temperature Control
The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger
temperature, and the electronic expansion valve opening is adjusted so that the actual discharge
pipe temperature becomes close to the target discharge pipe temperature. (Indirect SH
(superheating) control using the discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every
A
seconds. The opening degree of the electronic expansion valve is adjusted by the
following.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
The time depends on the opening of the electronic expansion valve.
09/12 class
15/18/24 class
A
(seconds)
720
540
All outdoor units
A
(seconds)
10 ~ 30
SC
(Subcooling)
SH
(Superheating)
The target discharge pipe
temperature is set as to become
the target SH.
The inclination does not change
depending on the operating condition.
(R23014)
Summary of Contents for FDMQ-R Series
Page 12: ...SiUS071735EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiUS071735EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 120: ...Check SiUS071735EA 109 Service Diagnosis 15 18 24 class R25105 1 2 3 4 Multimeter...
Page 122: ...Check SiUS071735EA 111 Service Diagnosis 15 18 24 class R20704 W V U DC_P1 DC_N1...
Page 140: ...Piping Diagrams SiUS071735EA 129 Appendix RX24RMVJU A 3D092249A...