SiUS071735EA
Troubleshooting
Service Diagnosis
68
4.5
Indoor Fan PCB Abnormality
Error Code
A8
Method of Error
Detection
Microcomputer checks the voltage state of the fan PCB.
Error Decision
Conditions
Overvoltage or voltage drop is detected on the fan PCB.
Supposed
Causes
Defective fan PCB
External factor such as noise
Troubleshooting
Caution
Be sure to turn off the power switch before connecting
or disconnecting connectors, or parts may be damaged.
Check for the indoor unit control
PCB (A1P) and the fan PCB
(A2P).
Connect the connector correctly.
NO
YES
YES
Is the
connector X3A on
the fan PCB connected
correctly?
Connect the connector correctly.
NO
YES
Is the
connector X70A on
the indoor unit control PCB
connected correctly?
Replace the harness.
YES
Is the harness
connecting X3A and X70A
broken?
NO
NO
Remove the external factor.
YES
Is there any external
factor such as noise?
Normal.
NO
Error is displayed
again.
Turn OFF the power supply
and then turn it ON again.
↓
Start operation with the
remote controller.
(R25085)
Summary of Contents for FDMQ-R Series
Page 12: ...SiUS071735EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiUS071735EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 120: ...Check SiUS071735EA 109 Service Diagnosis 15 18 24 class R25105 1 2 3 4 Multimeter...
Page 122: ...Check SiUS071735EA 111 Service Diagnosis 15 18 24 class R20704 W V U DC_P1 DC_N1...
Page 140: ...Piping Diagrams SiUS071735EA 129 Appendix RX24RMVJU A 3D092249A...