SiUS071735EA
Forced Cooling Operation
Trial Operation and Field Settings
114
2. Forced Cooling Operation
Outline
The forced cooling operation is allowed when both the following conditions are met.
1. The outdoor unit is not abnormal and not in the 3-minute standby mode.
2. The outdoor unit is not operating.
Protection functions have priority over all other functions during forced cooling operation.
Details
With Wired Remote Controller (BRC1E73)
With Wireless Remote Controller (BRC082A43)
1. Set to COOL operation using the remote
controller.
2. Press and hold
Cancel
button for 4 seconds
or longer. Service settings menu is
displayed.
3. Select
in the service
settings menu, and press
Menu/OK
button.
Basic screen returns and “Test Operation”
is displayed at the bottom.
4. Press
On/Off
button within 10 seconds, and
the forced cooling operation starts.
Forced cooling operation will stop
automatically after about 15 minutes.
To stop the operation, press
On/Off
button.
1. Press
button and select the COOL
operation.
2. Press
button twice.
“
TEST
”
is
displayed.
3. Press
button within 10 seconds, and
the forced cooling operation starts.
Forced cooling operation will stop
automatically after about 15 minutes.
To stop the operation, press
button.
Test Operation
Basic screen
1.
2.
3.
4.
Service Settings
menu screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Press On/Off button
(within 10 seconds).
Summary of Contents for FDMQ-R Series
Page 12: ...SiUS071735EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiUS071735EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 120: ...Check SiUS071735EA 109 Service Diagnosis 15 18 24 class R25105 1 2 3 4 Multimeter...
Page 122: ...Check SiUS071735EA 111 Service Diagnosis 15 18 24 class R20704 W V U DC_P1 DC_N1...
Page 140: ...Piping Diagrams SiUS071735EA 129 Appendix RX24RMVJU A 3D092249A...