FDYP125~2 FDQ125~250B8V3B
Split System air conditioners
4PW23694-1A

Installation manual

4

D

RAIN

 

CHECK

Make sure that the drain hose is firmly connected. Put some water
into the drain pan to check if the water flows smoothly.

F

IELD

 

WIRING

General instructions

Use copper wiring only.

Follow the "Wiring diagram" attached to the switchbox cover to
wire the outdoor unit, indoor units and remote controller. For
details on hooking up the remote controller, refer to the
"installation of the remote controller". For electric wiring work
also refer to 

"Internal wiring - parts table" on page 6

.

A circuit breaker capable of shutting down the power supply to
the entire system must be installed.

Be sure to use a dedicated power circuit (a power supply not
shared by another appliance).

Refer to the installation manual attached to the outdoor unit for
the size of the power supply electric wire connected to the
outdoor unit, the capacity of the circuit breaker and switch, and
wiring instructions.

Use a round crimp-style terminal for connection to the power
supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following
instructions.
-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When connecting wires of the same gauge, connect them in 
accordance with the figure below.

Do not connect wires of different gauges to the same grounding
terminal. Looseness in connection may deteriorate the
protection.

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the switchbox
cover. Make sure that the cover closes properly. Incomplete
connections could result in overheating, and in the worse case,
electric shock or fire.

Use the correct screwdriver to tighten the terminal screws. Small
screwdrivers can damage the screw head and prevent
appropriate tightening.
Over-tightening the terminal screws can damage the screws.
The standard tightening torque is 0.9 N•m.

Electrical characteristics

For details, refer to "Electrical data".

Specifications for field wire

Precautions on electrical wiring work

Before obtaining access to terminal devices, all supply circuits
must be interrupted.

Do not turn on the main switch until all the wiring is completed.
Make sure that the main switch has a contact separation of at
least 3 mm in all poles.

Methods of wiring units and connecting remote 
controller cords 

(See figure 6)

Wiring the units (power supply wiring)

Connect the interconnection wiring (from outdoor to indoor) to
the 1-2-3 terminal (1) using a separate power supply of the
indoor unit fan motor to the L-N terminal.

Remote controller code.
Connect the cords to the remote controller terminal (P1,P2) (No
polarity) (2).

Precautions

Do not clamp remote controller cords together with the other
wiring. Doing so may cause malfunction.

Do not place the controller where it is exposed to direct sunlight.
The LCD display may get discolored, failing to display the data.

Remote controller cords and wires connecting the units should
be located at least 50 mm from other electric wires. Not following
this guideline may result in malfunction.

If proper drainage is not carried out from the outdoor drain
pipes during air conditioning operation, chances are that
the pipe is clogged with dust and dirt. This may result in
water leakage from the indoor unit. Under such
circumstances, stop operation of the air conditioner and
consult your dealer or air conditioner service station.

All wiring must be performed by an authorised
electrician.
All components procured on the site and all electric
construction should comply with the applicable local
and national codes.

High voltage
In order to avoid electric shock, make sure to
disconnect the power supply 1 minute or more before
servicing the electrical parts. Even after 1 minute,
always measure the voltage at the terminals of main
circuit capacitors or electrical parts and, before
touching, make sure that those voltages are 50 V DC
or less.

In order to avoid electric shock, make sure that an
earth leakage breaker is installed.

Be sure the air conditioner is electrically earthed.
In order to avoid electric shock, make sure that the
unit is grounded and that the earth wire is not
connected to a gas or water pipe, lightning conductor
or telephone earth wire.

Never replace a fuse with that of a different ampere
rating or other wires when a fuse blows.
This may cause the unit to break down or cause a fire.

When connecting or disconnecting a power supply
cord, make sure that the current-carrying conductors
become taut before the earthing conductor.

Wire

Size (mm

2

)

Length

Between 

indoor units

H05VV-U4G

(1),(2)

(1) Shows only in case of protected pipes. Use H07RN-F in case of no protection.
(2) Run transmission wiring between the indoor and outdoor units through a conduit 

to protect against external forces, and feed the conduit through the wall together 
with refrigerant piping.

1

Unit - remote 

controller

Sheathed wire 

(2 wire)

(3)

(3) Use double insulation wire for remote controller (sheath thickness: 

1 mm) or run 

wires through a wall or conduit so that the user cannot come in contact with them.

0.75–1.25

Max. 500 m

(4)

(4) This length shall be the total extended length in the system of the group control.

Indoor fan 

power supply

Must comply with relevant local and national regulations

Summary of Contents for FDQ125B8V3B

Page 1: ...INSTALLATION MANUAL FDYP125B8V1 FDYP200B8V1 FDYP250B8V1 FDQ125B8V3B FDQ200B8V3B FDQ250B8V3B Split System air conditioners ...

Page 2: ... 2 2 1 4 5 3 1 2 4 1440 602 125 class 840 200 250 class P1 P2 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 P1 P2 P1 P2 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 7 P1 P2 1 2 3 P2 1 2 3 L N P1 1 2 3 P2 1 2 3 L N P1 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 2 1 1 2 3 4 5 6 7 8 9 ...

Page 3: ... atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus 23 tad ja lietoti atbilstoši ražotāja norādījumiem atbilst sekojošiem standartiem un citiem normatīviem dokumentiem 24 sú v zhode s nasledovnou ými normou ami alebo iným i normatívnym i dokumentom ami za predpokladu že sa používajú v súlade s našim návodom 25 ürünün talimatları...

Page 4: ...maintenance and service can be ensured Refer to figure 1 service space The power supply intake 1 the drain connection 2 gas pipe 3 and liquid pipe 4 connection should always be accessible for maintenance and service Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual for the outdoor unit Where there is no danger of fire due to leaka...

Page 5: ... in places exposed to the air flow from the unit or under the indoor unit It may cause incomplete combustion or deformation of the unit due to the heat Tick when checked Is the indoor unit fixed firmly The unit may fall down vibrate or make noise Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Condensate water may drip Does drainage flow smoothly Con...

Page 6: ...cting or disconnecting pipes to from the unit Refer to figure 4 Refer to the table below for the dimensions of flare nut spaces Because R407C R410A refrigerant is used apply ether or ester oil around the flare portions before connecting Coat here with ether oil or ester oil Refer to the table above to determine the proper tightening torque Overtightening may damage the flare and cause leaks Check ...

Page 7: ...e interconnection wiring from outdoor to indoor to the 1 2 3 terminal 1 using a separate power supply of the indoor unit fan motor to the L N terminal Remote controller code Connect the cords to the remote controller terminal P1 P2 No polarity 2 Precautions Do not clamp remote controller cords together with the other wiring Doing so may cause malfunction Do not place the controller where it is exp...

Page 8: ...rotect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank case heater for 6 hours 4 Set to cooling operation with the remote controller and start operation by pushing ON OFF button 5 Press Inspection Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate normally 7 Confirm function...

Page 9: ...or Sky Air series only for FDYP125 250 X33A Connector Adaptor for wiring X40A Connector remote on off forced off X60A X61A Connector interface adaptor for Sky Air series only for FDQ Wired remote controller BS1 ON OFF button BS2 Timer mode start stop button BS3 BS8 Programming timer button BS4 Temperature setting button up BS6 Operation mode selector button BS7 Timer on off button BS9 Temperature ...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23694 1A ...