Appendix:
Air conditioner nominal working condition and working range:
Test condition
Indoor side
Outdoor side
DB(°C)
WB(°C)
DB(°C)
WB(°C)
Nominal cooling
27
19
35
24
Nominal heating
20
–
7
6
Rated cooling
32
23
52
31
Low temp. cooling
21
15
18
–
Rated heating
27
–
24
18
Low temp. heating
20
–
–7
–8
Note:
The design of this unit conforms to the requirements of ISO13253 standard.
1.
The air volume is measured at the relevant standard external static pressure.
2.
Cooling (heating) capacity stated above is measured under nominal working conditions corresponding
3.
to standard external static pressure. The parameters are subject to change with the improvement of
products, in which case the values on nameplate shall prevail.