Tighten the hanger installing bolts (M8) at 4 places securely.
(Refer to Fig. 11)
(5)
When hanging the indoor unit, make sure to use the level to have better drainage and install it horizontally.
Also, if it is possible at the installation site, install so that the drain piping side is slightly lower.
(Refer to Fig. 12)
CAUTION
•
Setting the indoor unit at an angle opposite to the drain piping might cause a water leakage.
• Do not insert materials other than that specified into the clearance between the hanger and the
washer for hanger (3).
Unless the washers are properly attached, the hanging bolts may come off from the hanger.
A.
When the drain piping is tilted to the right, or to the right and back.
Place it level, or tilt it slightly to the right or the back. (Within 1°)
B.
When the drain piping is tilted to the left, or to the left and back.
Place it level, or tilt it slightly to the left or the back. (Within 1°)
WARNING
The indoor unit must be securely installed on a place that can withstand the mass.
If the strength is insufficient, the indoor unit may fall down and cause injuries.
Hanger
fixing screw
(M5)
Attachement
part
Hanger
Reinforcing plate (left/right)
When carrying the indoor unit,
do not hold the reinforcing plates.
Hanger installing
bolt (M8)
Fig. 11
A
A.B
B
≤
1˚
≤
1˚
≤
1˚
Fig. 12