DAMA-SM-21-001
Main Functions
Functions and Control
27
Cooling
The following drawings explain the principle of fan speed control for cooling.
Heating
The following drawings explain the principle of fan speed control for heating.
On heating mode, the indoor fan speed will be regulated according to the heat exchanger
temperature and the difference between the room temperature and the required target
temperature.
1.5 Dry
Mode
Outline
Program dry operation removes humidity. Since the microcomputer controls the airflow rate, the
FAN setting buttons are inoperable.
Details
The microcomputer automatically sets the airflow rate. The difference between the room
thermister temperature and the set temperature is divided into zones. Then, the unit operates in
an appropriate capacity for each zone to maintain the temperature and humidity at a
comfortable level.Zone B continues to stay for 120 seconds before the unit will turn to
thermostat ON.
Series Class
SL L
M
H
SH
FTX Series
09
219
249
322
431(C) 402(H)
466
12
210
247
316
436(C) 412 (H)
473
18
395
467
605
716
754
24
395
467
605
716
754
Room thermistor temperature – set temperature
Fan speed
+1.5°C
(+2.7°F)
+0.5°C
(+0.9°F)
+2°C
(+3.6°F)
+1.5°C
(+2.7°F)
H
L
Room thermistor temperature – set temperature
Fan speed
+2.5°C
(+4.5°F)
0°C
(0°F)
+3°C
(+5.4°F)
+1°C
(+1.8°F)
H
+0.5°C
(+0.9°F)
L