DAMA-SM-21-001
Main Functions
Functions and Control
29
1.7 Thermostat
Control
Outline
Thermostat control is based on the difference between the room thermistor temperature and the
set temperature.
Details
Thermostat OFF Conditions
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling/Dry/Heating: 2 minutes)
Cooling/Dry
Heating
Zone B
Zone B
Zone A
Zone A
OFF
OFF
ON
ON
Zone C
Zone C
–1.0°C
(–1.8°F)
Cooling : –0.5°C (–0.9°F)
Dry : –0.5°C (–0.9°F)
Cooling/Dry : –1.5°C (–2.7°F)
Room thermistor temperature – set temperature
OFF
OFF
ON
ON
0.5°C
(0.9°F)
1.5°C
(2.7°F)
A
B
C
Room temperature – set temperature