72
Reference
4.13 DC Fan Lock
Error Code
E7
Method of Error
Detection
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Error Decision
Conditions
The fan does not start in about 30 ~ 60 seconds (depending on the model) even when the
fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matter stuck in the fan
Defective fan motor
Defective outdoor unit PCB
Troubleshooting
Check No.16
Refer to P.90
YES
YES
NO
YES
NO
NO
YES
NO
Turn on the power.
Rotate the fan.
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor fan
motor.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Fan motor connector
disconnected?
Foreign matters in or
around the fan?
Fan rotates
smoothly?
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
Pulse signal generated?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution