DAMA-SM-21-001
Troubleshooting
Service Diagnosis
78
Reference
Reference
4.18 Position Sensor Abnormality
Error Code
H6
Description
Position Sensor Abnormality
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through
the position detection circuit.
Error Decision
Conditions
The compressor fails to start in about 15 seconds after the compressor run command signal
is sent.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Power supply voltage out of specification
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage out of specified range
Troubleshooting
Check No.18
Refer to P.91
Check No.20
Refer to P.92
Voltage as rated?
OK?
Normal?
Correct the power supply.
Replace the stop valve.
Replace the outdoor
unit PCB (main PCB).
Replace the outdoor unit
PCB (main PCB) / compressor
Reconnect the electrical
components or compressor
harnesses as specified.
Electrical
components or
compressor harnesses
connected as
specified?
Check No. 18
Check the discharge pressure.
Check No. 20
Check the short circuit of the
diode bridge.
YES
YES
YES
YES
NO
Check the power supply voltage.
Check the connection.
Turn off the power.
NO
NO
NO
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution