Actuator Check
DAMA-SM-21-001
91
Service Diagnosis
5.7 Installation Condition Check
Check No.17
5.8 Discharge Pressure Check
Check No.18
Installation condition check
OK
NG
YES
YES
NO
NO
NO
YES
Check the allowable
dimensions of the air
suction and
discharge area.
Is the discharged air
short-circuited?
Is the outdoor heat
exchanger very dirty?
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the outdoor temperature.
(The outdoor temperature
should be within the operation
range.)
Change the installation
location or direction.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
YES
YES
YES
NO
NO
NO
Is the stop valve open?
Open the stop valve.
Replace the compressor.
Discharge pressure check
Is the air filter or
indoor/outdoor heat
exchanger dirty?
Is the connection pipe
deformed?
Replace the pipe installed at
the site.
Clean the dirty air filter or
indoor/outdoor heat
exchanger.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution