Troubleshooting
SiMT041509E
63
Service Diagnosis
4.8
Unspecified Voltage (Between Indoor Unit and Outdoor
Unit)
Error Code
UA
Method of Error
Detection
The supply power is detected for its requirements (pair type is different from multi type) by the
indoor / outdoor transmission signal.
Error Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Disconnection of connector S92
Broken jumpers (wires) of connector S92
Troubleshooting
(R22028)
Caution
NO
YES
YES
YES
NO
NO
NO
YES
Match the compatible models.
OK?
Correct the connection.
Check the code numbers
(2P012345, for example) of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
Are the
connecting wires connected
property?
Reconnect the connector S92.
Connector S92
properly connected to the
PCB?
Replace the connector S92.
Jumpers (wires)
of the connector S92 cut or
broken?
Check the
combination of the
indoor
and outdoor unit.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for FTK(X)M-P Series
Page 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45...
Page 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition...