Troubleshooting
SiMT041509E
79
Service Diagnosis
4.20 Electrical Box Temperature Rise
Error Code
L3
Method of Error
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Error Decision
Conditions
With the compressor off, the radiation fin temperature is above
A
°C.
The error is cleared when the radiation fin temperature drops below
B
°C.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above
C
°C and stops when it drops below
B
°C.
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Troubleshooting
Check No.17
Refer to P.88
Check No.19
Refer to P.89
A
(°C)
B
(°C)
C
(°C)
90
75
81
Caution
WARNING
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above
C
°
C. The outdoor fan stops
when the radiation fin temperature
drops below
B
°
C.
(R21436)
YES
NO
YES
NG
NO
OK
NO
YES
Turn off the power. Then, turn on
the power to restart the system.
Check the radiation fin
temperature.
Radiation fin dirty?
Check No. 19
Check the outdoor fan.
Error again or outdoor
fan activated?
Replace the outdoor unit
PCB (main PCB).
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
Above
A
˚C?
Check the installation
condition.
Go to
Check No. 17
.
Summary of Contents for FTK(X)M-P Series
Page 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45...
Page 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition...