Service Diagnosis
84
5.2
Indoor Fan Motor Connector Output Check
Check No.02
1. Check the connection of connector.
2. Check the motor power supply voltage output (pins 4 - 7).
3. Check the motor control voltage (pins 4 - 3).
4. Check the rotation command voltage (pins 4 - 2).
5. Check the rotation pulse (pins 4 - 1).
5.3
Power Supply Waveforms Check
Check No.11
Measure the power supply waveform between No. 1 and No. 2 on the terminal board, and check
the waveform disturbance.
Check if the power supply waveform is a sine wave. (Fig.1)
Check if there is waveform disturbance near the zero-cross. (sections circled in Fig.2)
5.4
Electronic Expansion Valve Check
Check No.12
Conduct the followings to check the electronic expansion valve (EV).
1. Check if the EV connector is correctly connected to the PCB.
2. Turn the power off and on again, and check to see if the EV generates a latching sound.
3. If the EV does not generate a latching sound in the above step 2, disconnect the connector
and check the continuity using a multimeter.
4. Check the continuity between the pins 1 - 5, 2 - 5, 3 - 5, 4 - 5. If there is no continuity between
the pins, the EV coil is faulty.
5. If the continuity is confirmed in step 3, the outdoor unit PCB (main PCB) is faulty.
7
6
5
4
3
2
1
S1
(R19654)
Motor power supply voltage (310 ~ 340 VDC)
Unused
Unused
GND
Motor control voltage (15 VDC)
Rotation command voltage (1~ 6.5 VDC)
Rotation pulse input
Fig.1
Fig.2
(R1736)
(R1444)
Harness 5P
5P Connector
Check
S20
1 - 5
2 - 5
3 - 5
4 - 5
1 2 3 4 5
(R20506)
Summary of Contents for FTK(X)M-P Series
Page 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45...
Page 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition...