General Functionality
SIE-86
22
Main Function
The frequency command for every zone is stated below.
(Please note that an operation will not carry out in the commanded frequency sometimes in case a
protection control like a freeze-protection etc. will be actuated.)
3. Required fan speed
Fan speed changes the rotation speed every time when a thermostat switches over ON and OFF.
When the thermostat becomes Off, fan continues to operate 10 minutes more with low speed so as to
prevent recovery of humidity caused by reevaporation of the drain water, and then stops.
∗
For both H / J type
Night set mode
The night set mode is activated when the off timer is set. It restricts the operation frequency, to minimize
the noise.
∗
For both H / J type
Room temperature
Room temp. zone
Command frequency
H type (25 / 35)
J type (25 / 35)
Room temp. < 18˚C
A
0 / 0Hz
0 / 0Hz
except A
36 / 36Hz
34 / 34Hz
Room temp.
≥
18˚C
A
0 / 0Hz
0 / 0Hz
B
36 / 36Hz
34 / 34Hz
D
36 / 36Hz
40 / 40Hz
E
40 / 40Hz
42 / 42Hz
F
40 / 44Hz
42 / 42Hz
Fan rpm (thermostat ON)
H type (25 / 35)
J type (25 / 35)
Thermostat ON
800 / 800rpm
970 / 980rpm
Thermostat OFF
700 / 700rpm
800 / 800rpm
Thermostat ON and dry on powerful
operation
850 / 910rpm
1050 / 1050rpm
Item
Description
Drawing
cooling
The set temperature
stays on for one hour,
then decreases slightly
for economical
operation.
heating
The set temperature
stays on for one hour,
then increases slightly
for economical
operation.
0,5˚C
0,5˚C
0,5˚C
temperature shift
A
A
B
B
A
B
temperature s1˚C
temperature s0.5˚C
temperature setting
operation stops
at the set hours
1 hour
30 min.
Timer operation
Night set circuit on
+0.5˚C temperature shift
Temperature setting remains
When the outside temperature is lower than 27˚C and the room
temperature is at the set temperature.
When the outside temperature is 27˚C or higher.
(RL017)
2˚C
Thermostat
setting
Timer operation
Night set circuit on
1 hour later
(RL018)