SIE-86
General Functionality
Main Function
29
1.15
Peak-Cut Control Function (H / J Type)
Outline
In a heating operation, there will be anxiety that a head pressure excessively increases and exceeds the
permissible limit in an over load conditions.
For avoiding this fact, when the head pressure increases, frequency step down control is carried out for the
protection so that the head pressure will not exceed the permissible limit after detecting the temperature of
the indoor unit’s heat exchanger (saturation temperature equivalent to head pressure).
Processing
∗
J type makes DP1 ~ DP4 increase 2˚C in POWER FULL heating operation. There is no change in H
type even if POWER FULL is applied.
∗
DP : Peak cut temperature of heat exchanger
The restriction for frequency is not conducted in the return area by means of peak-cut control.
Frequency is increased approximately every 2 Hz/min. in the up-area.
Frequency alteration in the steady area is not conducted.
Frequency - down is carried out in the step down area approximately every 2 ~ 4 Hz/20sec.. (2 Hz for H
type, 4 Hz for J type)
Compressors stop in the stop area.
Setting a constant
H type
J type
DP0
67˚C
67˚C
DP1
58˚C
56˚C
DP2
56˚C
54˚C
DP3
55˚C
53˚C
DP4
48˚C
46˚C
Stop area
Step down
area
Return area
Up-area
Steady area
DP0
Heat exchanger temp. DC
Heat exchanger temp. DC
DP4
DP3
DP2
DP1
∗
This function has not time guard.
(RL025)