Problem Symptoms and Measures
SIE-86
54
Service Diagnosis
2. Problem Symptoms and Measures
Problem Symptom
Check Item
Details of Measure
Page No.
to be
referred
None of The Units Operates.
Check the power supply.
Check to make sure that the rated voltage is supplied.
—
Check the type of the indoor units.
Check to make sure that the indoor unit type is
compatible with the outdoor unit.
—
Check the outside air temperature.
Heating operation cannot be used when the outside
temperature is 30˚C or higher (only for heat pump
model), and cooling operation cannot be used when
the outside temperature is below 0 ˚C.
—
Diagnosis with indoor unit LED indication
—
—
Diagnosis with outdoor unit LED
indication
—
58
Check the remote controller addresses.
Check to make sure that address settings for the
remote controller and indoor unit are correct.
—
Operation Sometimes Stops.
Check the power supply.
A power failure of 2 to 10 cycles can stop air
conditioner operation. (Operation lamp OFF)
—
Check the outside air temperature.
Heating operation cannot be used when the outside
temperature is 30˚C or higher (only for feat pump
model), and cooling operation cannot be used when
the outside temperature is below 0˚C.
—
Diagnosis with indoor unit LED indication
—
—
Diagnosis with outdoor unit LED
indication
—
58
Some indoor units do not
operate.
Check the type of the indoor units.
Check to make sure that the indoor unit type is
compatible with the outdoor unit.
—
Diagnosis with indoor unit LED indication
—
—
Diagnosis with outdoor unit LED
indication
—
58
Equipment operates but does
not cool, or does not heat (only
for heat pump model).
Check for thermistor detection errors.
Check to make sure that the main unit’s thermistor
has not dismounted from the pipe holder.
—
Diagnosis with indoor unit LED indication
—
—
Diagnosis with outdoor unit LED
indication
—
58
Diagnosis by service port pressure and
operating current
Check for insufficient gas.
82
Large Operating Noise and
Vibrations
Check the output voltage of the power
transistor.
—
78
Check the power transistor.
—
—
Check the installation condition.
Check to make sure that the required spaces for
installation (specified in the Technical Guide, etc.) are
provided.
—
Si-86.book Page 54 Friday, June 23, 2000 10:26 AM