Troubleshooting
SIE-86
58
Service Diagnosis
5.2
Outdoor Units
4
: ON,
1
: OFF,
5
: Blinks
Green: Flashes when in normal condition
Red: OFF in normal condition
- : Not used for troubleshooting
∗
: Varies depending on the cases.
Note:
1. The indications in the parenthesis ( ) in the remote controller display column are displayed only when
system-down occurs.
2. When a sensor error occurs, check the remote controller display to determine which sensor is
malfunctioning.
If the remote controller does not indicate the error type, conduct the following operation.
*Turn the power switch off and back on again. If the same LED indication appears again immediately
after the power is turned on, the fault is in the thermistor.
*If the above condition does not result, the fault is in the CT.
3. The indoor unit error indication may take the precedence in the remote controller display.
Outdoor Unit LED Indication
Indication on the
remote controller
Description of The Fault
Details of Fault
(Refer to the
indicated
page.)
Green
Red
A
1
2
3
4
5
3
3
3
3
∗
Outdoor unit in normal condition
(Conduct a diagnosis of the indoor unit.)
—
5
3
3
4
4
(
UUU
U0000
)
Operation halt due to detection of insufficient gas.
5
4
3
4
3
(
EEEE5555
)
Abnormal discharge pipe temperature.
Operation halt due to IT activation.
5
3
4
4
3
EEEE666
6
Operation halt due to detection of compressor startup error.
69
5
3
3
3
4
—
Operation halt due to radiation fin temperature rise. (Protection
of driver overheating)
5
4
4
3
3
HHH
H8888
Operation halt due to detection of CT abnormality.
67
5
4
4
3
3
HHH
H9999
Operation halt due to outside air thermistor abnormality.
68
JJJJ3333
Operation halt due to discharge pipe thermistor abnormality, or
due to detection of disconnected discharge pipe thermistor.
68
JJJJ666
6
Operation halt due to outdoor unit heat exchanger thermistor
abnormality.
68
5
3
3
4
3
LLLL5555
Operation halt due to detection of output overcurrent.
70
5
3
4
3
4
EEEE888
8
Operation halt due to detection of input overcurrent.
74
5
4
3
4
4
—
Operation halt due to the freeze protection function.
5
4
3
4
4
—
Operation halt due to the freeze protection function or indoor
unit icing protection.
(Conduct a
diagnosis of the
indoor unit.)
4
∗
∗
∗
∗
∗
Faulty outdoor unit PCB
72
3
∗
∗
∗
∗
∗
Faulty outdoor unit PCB or signal transmitting/receiving circuit.
73
Si-86.book Page 58 Friday, June 23, 2000 10:26 AM