SIE-86
Troubleshooting
Service Diagnosis
59
5.3
Faulty PCB
(A1)
Remote Controller
Display
AAA
A1111
Indoor unit LED
Display
Method of
Malfunction
Detection
Evaluation of zero-cross detection of power supply by indoor unit.
Malfunction
Decision
Conditions
When there is no zero-cross detection in approximately 10 continuous seconds.
Supposed Causes
Faulty indoor unit PCB
Faulty connector connection
Troubleshooting
Note:
Connector Nos. vary depending on models.
Control connector......S35 and S26
Connector connection check
(note).
YES
Is it normal?
NO
Correct connections.
Replace PCBs (1) and/or (2), (3).
(RF001)
Si-86.book Page 59 Friday, June 23, 2000 10:26 AM