SIE-86
Troubleshooting
Service Diagnosis
67
5.11
Operation Halt Due to Detection of CT Error
(H8)
Remote Controller
Display
HHH
H8888
Outdoor unit LED
Display
A
5
1
4
2
4
3
3
4
3
Method of
Malfunction
Detection
CT errors are detected using the compressor's operating frequency and the input current detected by the
CT.
Malfunction
Decision
Conditions
When the compressor's operating frequency is more than 62 Hz and the CT input is less than 0.1 V.
∗
Inlet current 0.75 A
When a CT error is generated 4 times, the system shuts down.
The malfunction counter will be reset unless the emergency stop will take place within sixty minutes of
the compressor operation time (as integrated time) after the return from the malfunction (including the
other emergency stops).
Supposed Causes
Faulty power transistor
Breaking of wire or faulty connection of internal wiring
Faulty outdoor PCB (1).
Troubleshooting
Check No.3
Refer to P.76
Check No.11
Refer to P.81
Check No.3
Check capacitor voltage.
∗
Is
operation current on
power live like as
right figure?
NO
NO
NO
Is resistance value normal?
NO
Check rectifier input voltage
Is voltage
270±30 VDC?
Check No.11
Check rectifier.
Is voltage generated?
Does abnormality
display appear?
Operate unit.
Turn off power, and turn on again.
NO
YES
YES
YES
YES
YES
To section about thermistor
abnormalities
Replace outdoor unit PCB.
Replace outdoor unit PCB.
Replace rectifier (diode module).
Replace outdoor unit PCB.
Replace outdoor unit PCB.
2sec
Current
(Approx)
Capacitor will be charged
when MRM 10 is ON.
Current rize together
with frequency rize.
Time
(RF004)
Si-86.book Page 67 Friday, June 23, 2000 10:26 AM