Troubleshooting
SIE-86
68
Service Diagnosis
5.12
Operation Halt Due to Thermistor Error or Disconnection Detection
(J3,J6,H9)
Remote Controller
Display
JJJJ3333,,,, JJJJ666
6,,,, HHHH9999
Indoor unit LED
Display
A
5
1
4
2
4
3
3
4
3
Method of
Malfunction
Detection
Thermistor errors are detected using thermistor input voltage to micro computor. (Thermistor errors are
detected using the temperatures detected by the thermistors.)
Malfunction
Decision
Conditions
When the thermistor input during compressor operation is more than 4.96 V or less than 0.04 V.
∗
Value changes depends on models
Supposed Causes
Faulty connector connection
Faulty thermistor
Faulty PCB
Troubleshooting
Check No.5
Refer to P.79
JJJJ3333
: Discharge pipe thermistor
JJJJ666
6
: Outdoor unit heat exchanger thermistor
HHH
H9999
: Outside air thermistor
Correct the connection.
Replace the thermistor.
Replace the outdoor unit P.C.B.
Is it normal?
Check No. 5
Thermistor resistance check
Check the connector connection.
YES
YES
Is it normal?
NO
NO