Troubleshooting
SIE-86
74
Service Diagnosis
5.17
Operation Halt Due to Detection of Input Over Current
(E8)
Remote Controller
Display
EEEE888
8
Indoor unit LED
Display
A
5
5
5
5
1
3
2
4
3
3
4
4
Method of
Malfunction
Detection
Input over current is checked using the input current detected by the CT during compressor operation.
Malfunction
Decision
Conditions
When the CT input remains above the value shown in the below table for 2.5 seconds during compressor
operation.
Table for constant
Supposed Causes
Over current due to faulty compressor.
Over current due to faulty power transistor.
Over current due to faulty electrolytic capacitor of the main inverter circuit.
Over current due to faulty PCB (1).
Detection error due to faulty PCB (1).
Over current due to short-circuit.
Model
Input current (A)
RK(X)25, 35 Series
0.75