SIE-86
Check
Service Diagnosis
83
6.1.9
Inverter Units Hall IC Check
No.16
Check No.16
1. Check the connector connection.
2. With the power ON, operation OFF, and the connector connected, check the following.
∗
Output voltage of about 5 V between pins 1 and 3.
∗
Generation of 3 pulses between pins 2 and 3 when the fan motor is operating.
Failure of (1)
faulty PCB
Replace the PCB.
Failure of (2)
faulty hall IC
Replace the fan motor.
Both (1) and (2) result
Replace the PCB.
The connector has 3 pins, and there are two patterns of lead wire colors.
Si-86.book Page 83 Friday, June 23, 2000 10:26 AM