Troubleshooting
SiMX042215E
56
Part 6 Service Diagnosis
4. Troubleshooting
4.1 Error Codes and Description
: Displayed only when system down occurs.
Error
Codes
Description
Reference
Page
System
00
Normal
—
U0
Refrigerant shortage
U2
Low-voltage detection or over-voltage detection
U4
Signal transmission error (between indoor unit and
outdoor unit)
UA
Unspecified voltage (between indoor unit and outdoor
unit)
Indoor
Unit
A1
Indoor unit PCB abnormality
A5
Freeze-up protection control
A6
Indoor fan motor (DC Motor) or related abnormality
C4
Indoor heat exchanger thermistor or related abnormality
C9
Room temperature thermistor or related abnormality
Outdoor
Unit
E1
Outdoor unit PCB abnormality
E5
OL activation (compressor overload)
E6
Compressor lock
E7
DC fan lock
E8
Input overcurrent detection
F3
Discharge pipe temperature control
F6
High pressure control in cooling
F8
System shutdown due to temperature abnormality in
compressor
H0
Compressor system sensor abnormality
H6
Position sensor abnormality
H8
DC voltage/current sensor abnormality
H9
Outdoor temperature thermistor or related abnormality
J3
Discharge pipe thermistor or related abnormality
J6
Outdoor heat exchanger thermistor or related
abnormality
L3
Electrical box temperature rise
L4
Radiation fin temperature rise
L5
Output overcurrent detection
P4
Radiation fin thermistor or related abnormality
—
None
Unknown