SiMX042215E
Troubleshooting
Part 6 Service Diagnosis
59
4.4 Indoor Fan Motor (DC Motor) or Related Abnormality
Error Code
A6
Method of Error
Detection
The rotation speed detected by the microcomputer during fan motor operation is used to
determine abnormal fan motor operation.
The fan motor stops its rotation within 5 seconds after the operation starts.
Error Decision
Conditions
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
is less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
Remarkable decrease in power supply voltage
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective indoor unit PCB