Troubleshooting
SiMX042215E
74
Part 6 Service Diagnosis
Reference
Reference
Reference
4.14 Input Overcurrent Detection
Error Code
E8
Method of Error
Detection
An input overcurrent is detected by checking the input current value with the compressor
running.
Error Decision
Conditions
The current exceeds 7 ~ 10 A (depending on the model) for 2.5 seconds with the compressor
running.
The upper limit of the current decreases when the outdoor temperature exceeds a certain level.
Supposed
Causes
Outdoor temperature out of operation range
Defective compressor
Defective power module
Defective outdoor unit PCB
Short circuit
Troubleshooting
Check No.15
Refer to P.93
Check No.17
Refer to P.96
Check No.18
Refer to P.96
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input overcurrent
after the wires have been disconnected and reconnected for part replacement, check the wiring again.
(R21863)
NO
YES
YES
NO
Start operation and measure the
input current.
Check No. 18
Check the discharge pressure.
Check No. 17
Check the installation condition.
Check No. 15
Check with the inverter analyzer.
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Replace the outdoor unit
PCB (main PCB).
Correct the power supply
or replace the outdoor unit
PCB (main PCB).
Any LED off?
Inverter analyzer:
RSUK0917C
Input current flowing
above its stop level?