4.10 Outdoor Unit PCB Abnormality
Error Code
E1
Method of Error
Detection
The system checks if the microcomputer is working in order.
The system checks if the zero-cross signal comes in properly.
Error Decision
Conditions
The microcomputer program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
Defective outdoor unit PCB
Noise
Momentary drop of voltage
Momentary power failure
Troubleshooting
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Contin
u
o
u
sly O
N
, OFF
Blink
YES
(R24717)
N
O
Replace the o
u
tdoor
u
nit
PCB (main PCB).
Gro
u
nd the system.
Zero-cross signal
a
b
normality.
Replace the o
u
tdoor
u
nit
PCB (main PCB).
Check if the o
u
tdoor
u
nit is
gro
u
nded.
Is LED A
b
linking?
Gro
u
nded?
T
u
rn on the po
w
er again.