66
Installation and Maintenance
Service Manual
11. Removal Procedure
11.1 Removal Procedure of Indoor Unit
Warning: Be sure to wait for a minimum of 20 minutes
after turning off all power supplies and discharge the
refrigerant completely before removal.
a
b
Axile bush
Push out the axile bush on horizontal
louver. Bend the horizontal louver with
hand and then separate the horizontal
louver from the crankshaft of step motor
to remove it.
Horizontal louver
Location of step motor
Procedure
Step
1. Remove filter assembly
2. Remove horizontal louver
Front panel
Front
case
Right filter
Groove
Left filter
Open the front panel. Push the left filter
and right filter until they are separate from
the groove on the front panel.
Remove the left filter and right filter
respectively.
(1) display: Screw off the 2 screws that
are locking the display board. Separate
the display board from the front panel.
(2) display: Screw off the 2 screws that
are locking the display board.
Separate the panel rotation shaft from
the groove fixing the front panel and then
removes the front panel.
3. Remove panel and display
display
Front panel
Panel rotation
Groove
Panel
display
FTKS09SL216
FTXS09SL216
FTKS12SL216
FTXS12SL216