Troubleshooting
Service Diagnosis
137
4.21 Over-voltage Detection
Remote control
Display
U2
Method of
Malfunction
Detection
An abnormal voltage rise is detected by checking the specified over-voltage detection circuit.
Malfunction
Decision
Conditions
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer
(The voltage is over 400V).
The system will be shut down if the error occurs 255 times.
Clearing condition: Continuous run for about 10 minutes (normal)
Supposed
Causes
Supply voltage not as specified
Over-voltage detection circuit defective
PAM control part(s) defective
Troubleshooting
Note:
If the model doesn’t have SPM, replace the outdoor unit PCB.
Check the supply voltage.
Correct the power supply.
Check for such factors for a
long term.
Replace the SPM.
(Replace the outdoor unit
PCB.)
(R2957)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Supply voltage as
specified?
NO
YES
Turn on the
power again.
Error displayed again?
YES
Repeat a
couple of times.
NO
Disturbance factors
∗
Noise
∗
Power supply distortion
Summary of Contents for FTKS20CVMB
Page 19: ...List of Functions SiENBE04 401A 10 List of Functions...
Page 45: ...Specifications SiENBE04 401A 36 Specifications...
Page 81: ...Control Specification SiENBE04 401A 72 Function and Control...
Page 111: ...Instruction SiENBE04 401A 102 System Configuration...
Page 155: ...Check SiENBE04 401A 146 Service Diagnosis...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 401A 216 Removal Procedure...
Page 229: ...Others SiENBE04 401A 220 Others...