Control Specification
SiENBE04-401A
66
Function and Control
3.11 Electronic Expansion Valve Control
Outline
The following items are included in the electronic expansion valve control.
Electronic expansion valve is fully closed
1. Electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Open Control
1. Electronic expansion valve control when starting operation
2. Control when frequency changed
3. Control for defrosting (only for heat pump model)
4. Control when a discharge pipe temperature is abnormally high
5. Control when the discharge pipe thermistor is disconnected
Feedback Control
1. Discharge pipe temperature control
Detail
The followings are the examples of control which function in each mode by the electronic
expansion valve control.
(R2833)
(only for heat
pump model)
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Fully closed when power is turned ON
Open control when starting
(Control of target discharge pipe temperature)
Pressure equalizing control
Open control when starting
(Control of target discharge pipe temperature)
(Defrost control FD=1)
Pressure equalizing control
Open control when starting
Continue
Pressure equalizing control
Control when frequency changed
Control f
or abnor
mally high discharge
pipe temper
ature
When power is turned ON
Cooling operation
Stop
Heating operation
Stop
Heating operation
Control of discharge pipe
thermistor disconnection
Stop
Operation pattern
(only for heat
pump model)
: function
x
: not function
(only for heat pump model)
Summary of Contents for FTKS20CVMB
Page 19: ...List of Functions SiENBE04 401A 10 List of Functions...
Page 45: ...Specifications SiENBE04 401A 36 Specifications...
Page 81: ...Control Specification SiENBE04 401A 72 Function and Control...
Page 111: ...Instruction SiENBE04 401A 102 System Configuration...
Page 155: ...Check SiENBE04 401A 146 Service Diagnosis...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 401A 216 Removal Procedure...
Page 229: ...Others SiENBE04 401A 220 Others...