Troubleshooting
SiBE04-302
96
Service Diagnosis
4.5
Thermistor or Related Abnormality (Indoor Unit)
Remote
Controller
Display
C4
,
C9
Method of
Malfunction
Detection
The temperatures detected by the thermistors are used to determine thermistor errors.
Malfunction
Decision
Conditions
When the thermistor input is more than 4.96 V or less than 0.04 V during compressor
operation
∗
.
∗
(reference)
When above about 212°C (less than 120 ohms) or below about -50°C (more than 1,860 kohms).
Note:
The values vary slightly in some models.
Supposed
Causes
Faulty connector connection
Faulty thermistor
Faulty PCB
Troubleshooting
Check No.6
Refer to P.122
C4
:
Heat exchanger temperature thermistor
C9
:
Room temperature thermistor
Check the connector connection.
YES
Correct the connection.
Replace the thermistor.
(Replace the indoor unit PCB.)
Replace the indoor unit PCB.
Is it normal?
Is it normal?
(R1403)
NO
Check No. 6
Thermistor resistance check
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for FTKS25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function...
Page 31: ...Specifications SiBE04 302 22 Specifications...
Page 137: ...Check SiBE04 302 128 Service Diagnosis...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix...
Page 199: ...SiBE04 302 iv Index...