Troubleshooting
SiBE04-302
102
Service Diagnosis
Troubleshooting
Check No.5
Refer to P.121
Check No.6
Refer to P.122
Check No.11
Refer to P.125
Correct.
Reconnect.
Replace the four way valve
coil.
Replace the outdoor unit
PCB.
Reconnect in position.
Replace a defective
thermistor.
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
(R3040)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Four way valve coil
disconnected (loose)?
YES
YES
NO
Functioning
NO
Check No. 11
Check the refrigerant line.
Malfunctioning
l
Insufficient gas
l
Water mixed
l
Stop valve defective
Harness out of connector?
NO
YES
Disconnect the
harness from
the connector.
Resistance between
harnesses about
3k
Ω
±0.5k
Ω
?
Malfunctioning
Functioning
Check No. 5
Check the four way valve
switching output.
YES
NO
Any thermistor disconnected?
Malfunctioning
Functioning
Check No. 6
Check the thermistors.
Check the continuity of the four
way valve coil and harness.
Summary of Contents for FTKS25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function...
Page 31: ...Specifications SiBE04 302 22 Specifications...
Page 137: ...Check SiBE04 302 128 Service Diagnosis...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix...
Page 199: ...SiBE04 302 iv Index...