background image

English

10

6.

Drain piping.

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water 

flows smoothly.

3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.

[Figure of Hose Front End]

4) When extending the drain hose, use a commercially available 

extension hose with an inner diameter of 16 mm.
Be sure to thermally insulate the indoor section of the extension 
hose.

5) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with embed-
ded piping work, use any commercially available 
drain socket (nominal diameter 13mm) as a 
joint.

Refrigerant Piping Work

1.

Flaring the pipe end. 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward 

so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

WARNING

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

 !" #$%&' !()" )!(*+#

," &'-+&'"# #(.'.%$#/

0( 1$%2 &) 2"$3&11"#/

4( '(1 2*1 1!" "'#

(5 1!" !()" &' .%1"$/

φ

18

φ

16

φ

16

The drain hose provided 
to indoor unit.

Indoor unit 
drain hose

φ

16

Extension drain hose

Heat insulation tube
(Field supply)

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13mm)

The drain hose provided 
to indoor unit.

φ

18

Set exactly at the position shown below.

A

Flaring

Die

A

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

(Cut exactly at 

right angles.)

 Remove burrs

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

01_EN_3P207973-1E.fm  Page 10  Monday, August 23, 2010  4:21 PM

Summary of Contents for FTX20J2V1B

Page 1: ...it series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie Sp...

Page 2: ...06 95 EC Electromagnetic Compatibility 2004 108 EC 3P290872 1 Takayuki Fujii Managing Director 1st of Jun 2011 DAIKIN TCF 015 N11 01 2011 DEKRA NB0344 74736 KRQ EMC97 4957 3P290872 1 fm Page 1 Tuesday...

Page 3: ...clamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels I...

Page 4: ...ectronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from any television or radio set unit may cause i...

Page 5: ...e fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while...

Page 6: ...pipe hole gap with putty Mounting plate Clip Mark rear side Bottom frame Front grille How to attach the indoor unit Hook the claws of the bottom frame to the mounting plate If the claws are difficult...

Page 7: ...unting plate retention spots and Dimensions 770 Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liquid pipe end Gas pipe end The re...

Page 8: ...together with an insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor...

Page 9: ...Remove the insulation fixing screws on the right to remove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the...

Page 10: ...e on the right side of the indoor unit the work can be performed with the electrical component box attached Omit the steps involved with removing and installing the electrical component box in order t...

Page 11: ...component box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the flap 2 Install the electrical component box 1...

Page 12: ...ot use mineral oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations On...

Page 13: ...cal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to...

Page 14: ...for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will rest...

Page 15: ...13 T rk e MEMO 10_TR_3P207973 1E fm Page 13 Monday August 23 2010 4 55 PM...

Page 16: ...T rk e 14 MEMO 10_TR_3P207973 1E fm Page 14 Monday August 23 2010 4 55 PM...

Page 17: ...15 T rk e MEMO 10_TR_3P207973 1E fm Page 15 Monday August 23 2010 4 55 PM...

Page 18: ...3P291651 1 00_CV_3P207973 1E fm Page 2 Tuesday August 31 2010 4 40 PM U Nove hospody 1 1155 301 00 Plzen Skvrnany Czech republic Zandvoordestraat 300 B 8400 Ostende Belgium www daikineurope com...

Reviews: