Refrigerant Piping Work

2.

Refrigerant piping.

CAUTION

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque wrenches. 

2-1. Caution on piping handling. 

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending. 

2-2. Selection of copper and heat insulation materials.

• When using commercial copper pipes and fittings, observe the following:

1) Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045 kcal/(mh•°C))
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimen-

sions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 9.5mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm Min.

30mm or more

Thickness 0.8mm (C1220T-O)

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration oil to 

the inner surface of the 

flare.

Do not apply refrigeration 

oil to the flare nut avoid 

tightening with over torque.

[Apply oil]

Torque wrench

Piping union

Flare nut

Spanner

[Tighten]

Flare nut tightening torque

Gas side

Liquid side

3/8 inch

1/4 inch

32.7-39.9N 

 

 m

(330-407kgf 

 

 cm)

14.2-17.2N 

 

 m

(144-175kgf 

 

 cm)

 !""

#$ %& $"!'( )!* +,

!-!+"!."(/ )&-('

01( $"!'( 2&301

4+01 0!*( 0& 5((*

6+'0 &' 4!0(' &307

8( ,3'( 0&

*"!)( ! )!*7

9!+%

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

01_EN_3P207973-1E.fm  Page 11  Monday, August 23, 2010  4:21 PM

Summary of Contents for FTX20J2V1B

Page 1: ...it series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie Sp...

Page 2: ...06 95 EC Electromagnetic Compatibility 2004 108 EC 3P290872 1 Takayuki Fujii Managing Director 1st of Jun 2011 DAIKIN TCF 015 N11 01 2011 DEKRA NB0344 74736 KRQ EMC97 4957 3P290872 1 fm Page 1 Tuesday...

Page 3: ...clamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels I...

Page 4: ...ectronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from any television or radio set unit may cause i...

Page 5: ...e fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while...

Page 6: ...pipe hole gap with putty Mounting plate Clip Mark rear side Bottom frame Front grille How to attach the indoor unit Hook the claws of the bottom frame to the mounting plate If the claws are difficult...

Page 7: ...unting plate retention spots and Dimensions 770 Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liquid pipe end Gas pipe end The re...

Page 8: ...together with an insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor...

Page 9: ...Remove the insulation fixing screws on the right to remove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the...

Page 10: ...e on the right side of the indoor unit the work can be performed with the electrical component box attached Omit the steps involved with removing and installing the electrical component box in order t...

Page 11: ...component box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the flap 2 Install the electrical component box 1...

Page 12: ...ot use mineral oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations On...

Page 13: ...cal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to...

Page 14: ...for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will rest...

Page 15: ...13 T rk e MEMO 10_TR_3P207973 1E fm Page 13 Monday August 23 2010 4 55 PM...

Page 16: ...T rk e 14 MEMO 10_TR_3P207973 1E fm Page 14 Monday August 23 2010 4 55 PM...

Page 17: ...15 T rk e MEMO 10_TR_3P207973 1E fm Page 15 Monday August 23 2010 4 55 PM...

Page 18: ...3P291651 1 00_CV_3P207973 1E fm Page 2 Tuesday August 31 2010 4 40 PM U Nove hospody 1 1155 301 00 Plzen Skvrnany Czech republic Zandvoordestraat 300 B 8400 Ostende Belgium www daikineurope com...

Reviews: