Indoor Unit Installation

1.

Installing the mounting plate

• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points 

on the wall.

2) Secure the mounting plate to the wall with screws.

Recommended mounting plate retention spots and dimensions

2.

Boring a wall hole and installing wall embedded pipe

• For walls containing metal frame or metal board, be sure to use a wall 

embedded pipe and wall cover in the feed-through hole to prevent possible 
heat, electrical shock, or fire.

• Be sure to caulk the gaps around the pipes with caulking material to 

prevent water leakage.

1) Bore a feed-through hole of 65mm in the wall so it has a down slope 

toward the outside.

2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole gap with putty.

3.

Installing the indoor unit

• In the case of bending or curing refrigerant pipes, keep the following 

precautions in mind.
Abnormal sound may be generated if improper work is conducted.

1) Do not strongly press the refrigerant pipes onto the bottom frame.
2) Do not strongly press the refrigerant pipes on the front grille, either.

770

Place the pipe port cover
in this pocket.

Gas pipe end

Through-the-wall 
hole 

I

65

Recommended mounting plate 
retention spots (7 spots in all)

Place a leveler 
on these tabs.

44.5

44.5

48

337

285

170

48

50

170

116.5

117

337

213

237

Drain hose position

Liquid pipe end

Use a tape measure 
as shown.

Position the end of 
the tape measure at    .

The removed pipe 

port cover can be 

kept in the mounting 

plate pocket.

Mounting 
plate

Removed pipe
port cover

A

Inside

Outside

Caulking

Wall embedded pipe 
(field supply)

Wall hole cover
(field supply)

Wall embedded pipe 
(field supply)

65

3PEN393185-9T.book  Page 6  Monday, September 5, 2016  1:34 PM

Summary of Contents for FTX25KNV1B

Page 1: ...CONDITIONER INSTALLATION MANUAL R410A Split Series English Deutsch Fran ais Nederlands Espa ol Italiano E Portugues Pycc T rk e MODELS FTX25KNV1B FTX35KNV1B 3PEN393185 9T book Page 1 Monday September...

Page 2: ...vamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B...

Page 3: ...ic shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of wires may resul...

Page 4: ...r at any place where there is a danger of flammable gas leakage In the event of a gas leakage build up of gas near the air conditioner may cause a fire to break out While following the instructions in...

Page 5: ...ands under the centre of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2 Install 3 screws of the...

Page 6: ...ctor and pull the harness as shown in the figure 3 Replace the electrical wiring cover as it was and pull the harness around as shown in the figure Removal method of metal plate electrical wiring cove...

Page 7: ...the marked area at the lower part of the front grille to release the hooks If it is difficult to release remove the front grille 30mm or more from ceiling Front panel 50mm or more from walls on both...

Page 8: ...a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant pipes...

Page 9: ...arkings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through the...

Page 10: ...insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulation fi...

Page 11: ...DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECTOR FRAMEGROUND S L FLOATSWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P...

Page 12: ...ay cause overheating electri cal shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may caus...

Page 13: ...ral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts wh...

Page 14: ...mperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 U...

Page 15: ...To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the system is not to be used for s...

Page 16: ...3P393185 9T 2016 09 Copyright 2016 Daikin 3PEN393185 9T book Page 1 Monday September 5 2016 1 34 PM...

Reviews: